Mitsubishi Electric 800 Series Instruction Manual page 344

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

5.9.8
Input terminal function selection
Use the following parameters to select or change the input terminal functions.
Pr.
Name
178
STF terminal function
T700
selection
179
STR terminal function
T701
selection
180
RL terminal function
T702
selection
181
RM terminal function
T703
selection
182
RH terminal function
T704
selection
183
RT terminal function
T705
selection
184
AU terminal function
T706
selection
185
JOG terminal function
T707
selection
186
CS terminal function
T708
selection
187
MRS terminal function
T709
selection
188
STOP terminal function
T710
selection
189
RES terminal function
T711
selection
Pr.
Name
699
Input terminal filter
T740
*1
The initial value is for standard models.
*2
The initial value is for separated converter types.
 Input terminal function assignment
• Using Pr.178 to Pr.189, set the functions of the input terminals
• Refer to the following table and set the parameters.
Setting
Signal
name
0
RL
Pr.59 = 0 (initial value) Low-speed operation command
Pr.59  0
1
RM
Pr.59 = 0 (initial value) Middle-speed operation command
Pr.59  0
2
RH
Pr.59 = 0 (initial value) High-speed operation command
Pr.59  0
3
RT
Second function selection
4
AU
Terminal 4 input selection
5
JOG
Jog operation selection
Initial value
60
STF (Forward rotation command)
61
STR (Reverse rotation command)
0
RL (Low-speed operation command)
1
RM (Middle-speed operation command)
2
RH (High-speed operation command)
3
RT (Second function selection)
4
AU (Terminal 4 input selection)
5
JOG (Jog operation selection)
9999
No function
*1
MRS (Output stop)
24
X10 (Inverter run enable signal)
*2
10
25
STP (STOP) (Start self-holding
selection)
62
RES (Inverter reset)
Initial value
Setting range
9999
5 to 50 ms
9999
Function
Remote setting (setting clear)
*1
*1
Remote setting (deceleration)
Remote setting (acceleration)
*1
Initial signal
0 to 8, 10 to 14, 16, 18, 24, 25, 28,
33, 37 to 40, 46 to 48, 50, 51, 57,
58, 60, 62, 64 to 67, 70 to 73, 77
to 81, 84, 92, 94 to 98, 128, 129,
9999
0 to 8, 10 to 14, 16, 18, 24, 25, 28,
33, 37 to 40, 46 to 48, 50, 51, 57,
58, 61, 62, 64 to 67, 70 to 73, 77
to 81, 84, 92, 94 to 98, 128, 129,
9999
0 to 8, 10 to 14, 16, 18, 24, 25, 28,
33, 37 to 40, 46 to 48, 50, 51, 57,
58, 62, 64 to 67, 70 to 73, 77 to 81,
84, 92, 94 to 98, 128, 129, 9999
Description
Set the time to delay the input terminal response.
No input terminal filter
Related parameter
Pr.4 to Pr.6, Pr.24 to Pr.27, Pr.232 to
Pr.239
Pr.59
Pr.4 to Pr.6, Pr.24 to Pr.27, Pr.232 to
Pr.239
Pr.59
Pr.4 to Pr.6, Pr.24 to Pr.27, Pr.232 to
Pr.239
Pr.59
Pr.44 to Pr.51, Pr.450 to Pr.463, Pr.569,
Pr.832, etc.
Pr.267
Pr.15, Pr.16
5.9 (T) Multi-Function Input Terminal Parameters
3
Setting range
4
5
5
5
6
7
8
9
10
Refer to
page
226
197
226
197
226
197
348
318
224
343
5. PARAMETERS