5.10.3
Offline auto tuning for a PM motor (motor constants
tuning)
PM
PM
PM
The offline auto tuning for a PM motor enables the optimal operation of a PM motor.
• Automatic measurement of motor constants (offline auto tuning) enables optimal operation of motors for PM motor control
even when motor constants vary or when the wiring distance is long.
For the offline auto tuning under Advanced magnetic flux vector control, refer to
Pr.
Name
684
Tuning data unit switchover
C000
1002
Lq tuning target current
C150
adjustment coefficient
71
Applied motor
C100
80
Motor capacity
C101
81
Number of motor poles
C102
9
Electronic thermal O/L relay
C103
83
Rated motor voltage
C104
84
Rated motor frequency
C105
702
Maximum motor frequency
C106
707
Motor inertia (integer)
C107
724
Motor inertia (exponent)
C108
96
Auto tuning setting/status
C110
90
Motor constant (R1)
C120
92
Motor constant (L1)/d-axis
C122
inductance (Ld)
93
Motor constant (L2)/q-axis
C123
inductance (Lq)
859
Torque current/Rated PM motor
C126
current
706
Induced voltage constant (phi f) 9999
C130
Initial
Setting range
value
0
0
1
9999
50 to 150%
9999
0
0 to 6, 13 to 16, 8090, 8093,
8094, 9090, 9093, 9094
9999
*1
0.4 to 55 kW
*2
0 to 3600 kW
9999
9999
2, 4, 6, 8, 10, 12
9999
Inverter
*1
0 to 500 A
rated
*2
0 to 3600 A
current
575 V
0 to 1000 V
9999
10 to 400 Hz
9999
9999
0 to 400 Hz
9999
9999
10 to 999, 9999
9999
0 to 7, 9999
0
0, 11, 101
1
9999
*1*3
0 to 50 Ω, 9999
*2*3
0 to 400 mΩ, 9999
9999
*1*3
0 to 500 mH, 9999
*2*3
0 to 50 mH, 9999
9999
*1*3
0 to 500 mH, 9999
*2*3
0 to 50 mH, 9999
9999
*1*3
0 to 500 A, 9999
*2*3
0 to 3600 A, 9999
0 to 5000 mV/(rad/s)
9999
page
353.
Description
Internal data converted value
The value is indicated with "A, Ω, mH or
mV".
Perform adjustment if the overcurrent
protective function is activated during
tuning.
No adjustment
By selecting a motor, the thermal
characteristic and motor constant of each
motor are set.
Applied motor capacity setting.
V/F control
Set the number of motor poles.
V/F control
Set the rated motor current.
Set the rated motor voltage (V).
Set the rated motor frequency (Hz).
The inverter internal data is used. Use the
correct setting according to the motor
specification.
Set the maximum frequency of the motor.
Pr.84 setting is used.
Set the motor inertia.
9999: The inverter internal data is used.
No offline auto tuning.
Performs offline auto tuning without
rotating the motor.
Tuning data
(The value measured by offline auto
tuning is automatically set.)
9999: The inverter internal data is used.
Set this parameter according to the PM
*3
motor specifications.
The value calculated by the motor
constant parameter setting is used.
5.10 (C) Motor constant parameters
3
4
5
5
5
6
7
8
9
10
363
5. PARAMETERS