Overview of Alarms
200: Below the valid values.
201: Above the valid values.
202: Cannot be accessed from the Basic Operator Panel (BOP).
203: Cannot be read from the Basic Operator Panel (BOP).
204: Write access not permitted.
Remedy:
- enter the correct value into the specified parameter.
- identify the parameter that narrows (restricts) the limits of the specified parameter.
201043
<location>Fatal error when downloading a project
Reaction:
OFF2 (OFF1, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
A fatal error was detected when downloading a project using the commissioning (start-up)
software.
Fault value (r0949, decimal):
1: Device status cannot be changed to Device Download (drive object ON?).
2: Drive object ID incorrect
3: A drive object that has already been deleted is deleted again.
4: Deletes drive object that has already been registered for generation.
5: Deletes a drive object that no longer exists.
6: Generating an undeleted drive object that already existed.
7: Regeneration of a drive object already registered for generation.
8: Maximum number of drive objects that can be generated exceeded.
9: Error while generating a device drive object.
10: Error while generating target topology parameters (p9902 and p9903).
11: Error when generating a drive object (global component).
12: Error when generating a drive object (drive component).
13: Unknown drive object type.
14: Drive status cannot be changed to Ready (p0947 and p0949).
15: Drive status cannot be changed to Drive Download.
16: Device status cannot be changed to Ready.
17: It is not possible to download the topology. The component wiring should be checked,
taking into account the various messages/signals.
18: A new download is only possible if the factory settings are re-established for the drive
unit.
19: The slot for the option module has been configured several times (e.g. CAN and COMM
BOARD)
20: The configuration is inconsistent (e.g. CAN for control unit, however no CAN configured
for drive objects - active line module, servo or vector).
Remedy:
- use the actual version of the commissioning software.
- modify the offline project and carry-out a new download (e.g. compare the number of drive
objects, motor, encoder, power module in the offline project and at the drive).
- change the drive system (is a drive rotating or is there a message/signal?).
- carefully note any other messages/signals and remove their cause.
201044
<location>CU CompactFlash: Message description incorrect
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
An error was detected when loading the message descriptions (FDxxxyyy.ACX) saved on
the CompactFlash Card.
Fault value (r0949, hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
Replace the CompactFlash Card.
201045
<location>CU CompactFlash: Configuration data invalid
Reaction:
NONE
Acknowledge:
NONE