08/2005
Cause:
The code numbers of the power modules do not match.
Fault value (r0949, decimal):
Parameter in which the first different power module code number was detected.
Remedy:
For parallel circuit configurations, only power modules with identical power module data
may be used.
205056
<location>Parallel circuit configuration: Power module EPROM versions
differ
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The EEPROM versions of the power modules do not match.
Fault value (r0949, decimal):
Parameter in which the first different version number was detected.
Remedy:
For parallel circuit configurations, only power modules with identical EEPROM versions
may be used.
205057
<location>Parallel circuit configuration: Power module firmware
versions differ
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The firmware versions of the power modules connected in parallel do not match.
Fault value (r0949, decimal):
Parameter in which the first different version number was detected.
Remedy:
For parallel circuit configurations, only power modules with identical firmware versions may
be used.
205058
<location>Parallel circuit configuration: VSM EEPROM versions differ
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The EEPROM versions of the voltage sensing modules (VSM) do not match.
Fault value (r0949, decimal):
Parameter in which the first different version number was detected.
Remedy:
For parallel circuit configurations, only voltage sensing modules (VSM) with identical
EEPROM versions may be used.
205059
<location>Parallel circuit configuration: VSM firmware versions differ
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The firmware versions of the voltage sensing modules (VSM) do not match.
Fault value (r0949, decimal):
Parameter in which the first different version number was detected.
Remedy:
For parallel circuit configurations, only voltage sensing modules (VSM) with identical
firmware versions may be used.
205060
<location>Parallel circuit configuration: Power module firmware version
does not match
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
Firmware from version V02.30.01.00 is required when connecting the power modules in
parallel.
Remedy:
Update the firmware of the power modules (at least V02.30.01.00).
205061
<location>Parallel infeed circuit, number of VSM
Reaction:
NONE
Acknowledge:
IMMEDIATELY
© Siemens AG, 2005. All rights reserved
SINUMERIK 840D sl/840D/840Di/810D Diagnostics Guide (DA), 08/2005 Edition
Overview of Alarms
2-679