08/2005
240887
<location>CU DRIVE-CLiQ: Component faulted
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
Fault detected on the DRIVE-CLiQ component involved. Faulty hardware cannot be
excluded.
Fault value (r0949, hexadecimal):
20: Error in the telegram header.
23: Receive error: The telegram buffer memory contains an error.
42: Send error: The telegram buffer memory contains an error.
43: Send error: The telegram buffer memory contains an error.
60: Response received too late during runtime measurement.
61: Time taken to exchange characteristic data too long.
Remedy:
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
- check the electrical cabinet design and cable routing for EMC compliance
- if required, use another DRIVE-CLiQ socket (p9904).
- replace the component involved.
240895
<location>CU DRIVE-CLiQ: Cyclic data transfer error
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communications error has occurred between the control unit and the
controller extension involved.
Fault value (r0949, hexadecimal):
0B: Synchronization error during alternating cyclic data transfer.
Remedy:
- carry-out a POWER ON.
See also: p9915
249150
<location>Cooling system: Fault occurred
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The cooling system signals a general fault.
Remedy:
- check the wiring between the cooling system and the input terminal (terminal module).
- check the external control unit for the cooling system.
See also: p0266
249151
<location>Cooling system: Conductivity has exceeded the fault
threshold
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The conductivity of the cooling water has exceeded the selected fault threshold (p0269[2]).
See also: p0266
Remedy:
Check the device to de-ionize the cooling water.
249152
<location>Cooling system: ON command, feedback signal missing
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The feedback signal of the ON command of the cooling system is missing.
- after the ON command, the feedback signal has not been received within the selected
starting time (p0260).
- the feedback signal has failed in operation.
See also: p0260, r0267
Remedy:
- check the wiring between the cooling system and the input terminal (terminal module).
- check the external control unit for the cooling system.
© Siemens AG, 2005. All rights reserved
SINUMERIK 840D sl/840D/840Di/810D Diagnostics Guide (DA), 08/2005 Edition
Overview of Alarms
2-815