Overview of Alarms
- Alarm display.
- NC Stop on alarm.
Remedy:
Use newer module.
Program Con-
Switch control OFF - ON.
tinuation:
311717
Axis %1 drive %2 SSI transmission timeout
Parameters:
%1 = NC axis number
%2 = Drive number
Definitions:
SSI transmission must be able to finish within one position control cycle. This is not possi-
ble with its current parameterization.
Reactions:
- Mode group not ready.
- Channel not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
Remedy:
Either increase the position control cycle of the NC or increase the SSI transmission rate
(MD_5011 $MD_ACTUAL_VALUE_CONFIG bits 14 and 15).
The following transmission rates are possible: 100 kHz, 500 kHz, 1 MHz and 2 MHz. Cau-
tion: It might be possible that the length of the encoder cable does not allow an increase
in frequency!
Program Con-
Switch control OFF - ON.
tinuation:
380001
Profibus-DP: startup error, reason %1 parameter %2 %3 %4.
Parameters:
%1 = Cause of the error
%2 = Parameter 1
%3 = Parameter 2
%4 = Parameter 3
Definitions:
An error occurred during startup of the PROFIBUS DP master.
Overview: Cause of the error, Par 1, Par 2, Par 3:
• 01 = DPM version, DPM version, DPA version, --
• 02 = DPM ramp-up timeout, DPM actual value status, DPM setpoint value status, --
• 03 = DPM ramp-up status, DPM actual value status, DPM setpoint value status, DPM
error code
• 04 = DPM ramp-up error, DPM actual value status, DPM setpoint value status, DPM
error code
• 05 = DPM-PLL sync error, --, --, --
• 07 = alarm queue too long, Actual number, Setpoint number, --
• 08 = unknown client, Client ID, --, --
• 09 = Client version, Client ID, Client version, DPA version
• 10 = too many clients, Client number, Max. number of clients, --
• 11 = log.basic address used several times; bus no.; slot no.; log.basic address --
• 20 = PB slave address used several times, slave address --
• 21 = PB slave address unknown, slave address, --
• 22 = Erroneous configuration telegram, slave address, error code, --
• 23 = OMI incompatible (data), Version drive, Version CDA --
• 24 = OMI incompatible (driver), Version drive, Version CDA --
• 25 = CPI initialization failed, error code
2-924