Overview of Alarms
Remedy:
- check the parameter involved.
- check the macro file and BICO interconnection.
See also: p0015, p0700, p1000, p1500
207083
<location>Macro: ACX file not found
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The ACX file (PM file) to be executed was not able to be found in the appropriate directory.
Fault value (r0949, decimal):
Parameter number with which the execution was started.
See also: p0015, p0700, p1000, p1500
Remedy:
- check whether the file is saved in the appropriate directory on the CompactFlash Card.
Example:
If p0015 = 1501 is set to 1501, then the selected ACX file must be located in the following
directory:
... /PMACRO/DEVICE/P15/PM001501.ACX
207084
<location>Macro: Condition for WaitUntil not fulfilled
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The wait condition set in the macro was not fulfilled in a certain number attempts.
Fault value (r0949, decimal):
Parameter number for which the condition was set.
Remedy:
Check and correct the conditions for the WaitUntil loop.
207085
<location>Drive: Open-loop/closed-loop control parameters changed
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
Parameters of the open-loop/closed-loop control had to be changed as they exceeded
dynamic limits as a result of other parameters.
Fault value (r0949, decimal):
The fault value includes the modified parameter number.
See also: p0640, p1082, p1300, p1800
Remedy:
It is not necessary to change the parameters as they have already been correctly limited.
207090
<location>Drive: Upper torque limit less than the lower torque limit
Reaction:
OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The upper torque limit is lower than the lower torque limit.
Remedy:
P1 must be >= P2 if parameter P1 is connected to p1522 and parameter P2 to p1523.
207100
<location>Drive: Sampling times cannot be reset
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
When resetting drive parameter (p0976) sampling times cannot be reset using p0111,
p0112, p0115.
Fault value (r0949, decimal):
Parameter whose setting prevents the sampling times being reset.
See also: p0110
Remedy:
- continue to work with the set sampling times.
- before resetting the drive parameters, set the basic clock cycle p0110[0] to the original
value.
See also: p0110
2-688
SINUMERIK 840D sl/840D/840Di/810D Diagnostics Guide (DA), 08/2005 Edition
© Siemens AG, 2005. All rights reserved
08/2005