Overview of Alarms
206350
<location>Infeed: Measured line frequency too high
Reaction:
NONE
Acknowledge:
NONE
Cause:
The actual line frequency f_line is higher than the parameterized alarm threshold (f_line >
p0211 * p0284).
The alarm can be output in two operating states:
1. During the power-on phase of the infeed unit.
Consequence:
Synchronization of the infeed to the line supply is interrupted and is restarted.
2. While the infeed is operational.
Consequence:
The infeed remains in the operating (run) state and alarm A6350 is output. This signifies a
critical operational fault.
Alarm value (r2124, floating point):
Actual line frequency determined.
See also: p0284
Remedy:
- check the parameterized line frequency and if required change (p0211).
- check the alarm threshold (p0284).
- check the line supply.
- check the line supply quality.
See also: p0211, p0284
206351
<location>Infeed: Measured line supply frequency too low
Reaction:
NONE
Acknowledge:
NONE
Cause:
The actual line frequency f_line is lower than the parameterized alarm threshold (f_line <
p0211 * p0285).
The alarm can be output in two operating states:
1. During the power-on phase of the infeed unit.
Consequence:
Synchronization of the infeed to the line supply is interrupted and is restarted.
2. While the infeed is operational.
Consequence:
The infeed remains in the operating (run) state and alarm A6351 is output. This signifies a
critical operational fault.
Alarm value (r2124, floating point):
Actual line frequency determined.
See also: p0285
Remedy:
- check the parameterized line frequency and if required change (p0211).
- check the alarm threshold (p0285).
- check the line supply.
- check the line supply quality.
See also: p0211, p0285
206400
<location>Infeed: Line supply data identification selected/active
Reaction:
NONE
Acknowledge:
NONE
Cause:
Line supply data identification selected/active.
The line inductance and the DC link capacitance are measured at the next pulse enable.
See also: p3410
Remedy:
No remedial action required.
206500
<location>Infeed: Line synchronization not possible
Reaction:
OFF2 (OFF1)
Acknowledge:
IMMEDIATELY (POWER ON)
2-684
SINUMERIK 840D sl/840D/840Di/810D Diagnostics Guide (DA), 08/2005 Edition