Accessing Plc By Fx Configurator-Fp - Mitsubishi Electric GT1685 Connection Manual

Got1000 series
Table of Contents

Advertisement

23.6.12 Accessing PLC by FX
Configurator-FP
This section explains the procedure to set the FA
transparent function of FX Configurator-FP with an
example of connecting to FXCPU.
1.
Click [Connection setup] for [Online] on FX
Configurator-FP.
2.
Check-mark either of the following in [PC side].
When connecting the GOT and PC with serial
Mark the [RS-232 (FX-USB-AW/FX3U-USB-BD
Included)] checkbox.
When connecting the GOT and PC with USB
Mark the [USB(GOT Transparent)] checkbox.
3.
Click [Comm. Test].
4.
After the communication test is completed, check that
the GOT is correctly connected to the FXCPU.
23 - 74
23. FA TRANSPARENT FUNCTION
23.6 Personal Computer Side Setting
23.6.13 Accessing by FX3U-ENET-L
Configuration tool
This section explains the procedure to set the FA
transparent function of the FX3U-ENET-L Configuration
tool.
1.
Click [Transfer setup] on the FX3U-ENET-L
Configuration tool.
2.
Mark the [Serial port/USB] checkbox in [Connecting
interface].
3.
Check-mark either of the following in [Serial port/
USB] of [Connecting interface].
When connecting the GOT and PC with serial
Mark the [RS-232C (include FX-USB-AW/FX3U-USB-
BD)] checkbox.
When connecting the GOT and PC with USB
Mark the [USB (GOT Transparent mode)] checkbox.
4.
Click [Connection test]