Connecting To Cc-Link Module (Melsec Iq-R Series) With Ver.1/Ver.2 Compatibles Mixed - Mitsubishi Electric GT1685 Connection Manual

Got1000 series
Table of Contents

Advertisement

13.4.3 Connecting to CC-Link module
(MELSEC iQ-R Series) with
Ver.1/Ver.2 compatibles mixed
This section describes the setting of the GOT and CC-Link
module (MELSEC iQ-R Series) with Ver.1/Ver.2
compatibles mixed in the following system configuration.
POINT
POINT
POINT
CC-Link module (MELSEC iQ-R Series)
For details of the CC-Link module (MELSEC iQ-R
Series), refer to the following manual.
Manuals of MELSEC iQ-R Series
System configuration
■ [Controller Setting] of GT Designer3
<GOT (Ver.1 compatible)>
(Use default value for settings other than the following.)
*1
<CC-Link module>
(Use default value for settings other than the following.)
Type
: Master station
Station No.
: Station No. 0
Mode
: Remote net (Ver.2 mode)
All connect count
: 2
Transmission speed : 156kbps
■ Unit parameter setting of GX Works3
*1
The CC-Link module is mounted on the base unit slot 0.
The Start I/O No. of the CC-Link module is set to "0".
13 - 18
13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
13.4 PLC Side Setting
Station type
: Intelligent device
station
Station No.
: Station No. 1
Number of stations
:
Exclusive station 1
occupied
Transmission speed
:
156kbps
<GOT (Ver.2 compatible)>
(Use default value for settings other
than the following.)
Station type
: Intelligent device
station
Station No.
: Station No. 2
Expanded cyclic setting
:
Single
Number of stations
:
Exclusive station
occupied
Transmission speed
:
156kbps
Unit parameter setting of GX Works3
(1) [Unit parameter] of GX Works3
(a) Unit parameter
Item
Station type
Mode
Station No.
*1
Transmission speed
Parameter setting
: Necessary
*1
Adjust the settings with GOT settings.
(b) Link refresh setting
Item
Special relay (SB) refresh
device
Special register (SW)
refresh device
Remote input (RX) refresh
device
Remote output (RY) refresh
device
Remote register (RWr)
refresh device
: Necessary
Setting
necessity at
Set value
GOT
connection
Master station
Remote net (Ver.2
mode)
0 (fixed)
156kbps
Engineering tool
: As necessary
: Not necessary
Setting
necessity at
Set value
GOT
connection
-
-
Set as necessary.
: As necessary
: Not necessary