8.3 GOT Side Settings
8.3.1
Setting communication
interface (Communication
settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: MITSUBISHI ELECTRIC
• Controller Type: Set according to the Controller
Type to be connected.
• I/F: Interface to be used
• Driver:
Ethernet(MELSEC), Q17nNC, CRnD-700
Ethernet(FX), Gateway
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
8.3.2 Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
8.3.2
Make the settings according to the usage environment.
GT16, GT14
3.
4.
Item
GOT NET No.
GOT PLC No.
Click!
GOT
*2
IP Address
Subnet Mask
Default
*2
Gateway
Ethernet
Download Port
*2
No.
GOT
Communication
*4
Port No.
Retry
Startup Time
Timeout Time
*1
Delay Time
Communication detail settings
Description
Set the network No. of the GOT.
(Default: 1)
Set the station No. of the GOT.
*3
(Default: 1)
Set the IP address of the GOT.
(Default: 192.168.3.18)
Set the subnet mask for the sub
network. (Only for connection via
router)
*2
If the sub network is not used, the
default value is set.
(Default: 255.255.255.0)
Set the router address of the default
gateway where the GOT is connected.
(Only for connection via router)
(Default: 0.0.0.0)
Set the GOT port No. for Ethernet
download.
(Default: 5014)
Set the GOT port No. for the
connection with the Ethernet module.
• For Ethernet (MELSEC), Q17nNC,
and CRnD-700
(Default: 5001)
• For Ethernet(FX), Gateway
(Default: 5019)
Set the number of retries to be
performed when a communication
timeout occurs.
When receiving no response after
retries, the communication times out.
(Default: 3times)
Specify the time period from the GOT
startup until GOT starts the
communication with the PLC CPU.
(Default: 3sec)
Set the time period for a
communication to time out.
(Default: 3sec)
Set the delay time for reducing the
load of the network/destination PLC.
(Default: 0ms)
8. ETHERNET CONNECTION
8.3 GOT Side Settings
1
2
3
4
Range
1 to 239
1 to 64
0.0.0.0 to
255.255.255.255
5
0.0.0.0 to
255.255.255.255
0.0.0.0 to
255.255.255.255
6
1024 to 5010,
5014 to 65534
(Except for 5011, 5012,
5013 and 49153)
1024 to 5010,
5014 to 65534
(Except for 5011, 5012,
5013 and 49153)
7
0 to 5times
3 to 255sec
8
1 to 90sec
0 to 10000
(
10ms)
8 - 17