When connecting the GOT multi-drop
connection
FA transparent function is available for each GOT in the
GOT multi-drop connection system.
(1) Standard monitor OS installation, Communication
driver writing
When using FA transparent function in GOT multi-drop
connection, the writing of the standard monitor OS and
communication driver to the GOT from GT Designer3
(Version 1.18U or later), as well as the writing of the
standard monitor OS and communication driver to the
serial multi-drop connection unit are required.
(2) Number of personal computers
Only one personal computer can be connected to the
multi-drop connection system.
Only one personal computer
(3) Monitor speed of GOT
The monitoring performance slows down according to
the number of monitoring GOTs. While using FA
transparent function, the monitoring performance of the
whole multi-drop system decreases. As a result,
timeout error may occur in GOTs in the system.
When connecting the GOT and personal
computer with modem connection
When using the FA transparent function with a modem,
the communication settings of compatible software,
modem connection tool, modem and GOT must be set
correctly to communicate with the GOT. If not correctly
set, the communication cannot be performed.
When connecting the GOT and personal
computer with serial or USB
When the operations shown below are executed, the
operation is executed in the PLC. However, the display
on the GOT may stop temporarily or the display of
timeout may appear on GX Works3, GX Works2.
*1
Operation
Applied for the following operations
• Remote Reset
specifying the currently selected
station.
• Remote RUN
• Remote STOP
• Remote PAUSE
Applied for the following operations
• Remote STEP-RUN
specifying all the station.
• Remote Reset
• Remote latch clear
• Write clock data
• CC IE Control diagnostics
(Link startup/stop)
• CC IE Field diagnostics
(Link startup/stop)
*1
The remote operations only of when the connection type
between the GOT and CPU is the direct CPU connection or
computer link connection are applied.
QCPU, FXCPU
QnACPU
ACPU
Motion controller CPU
(A series)
(1) Monitoring performance of the GOT is temporarily
(2) The GOT cannot respond to the touch switch operation
(3) Writing to PLC results in a system alarm occurrence
(4) While setting the monitor conditions, do not perform
Remark
(5) When the time check of GX Works3, GX Works2, GX
23.7.2 When using GX Works3, GX
Works2, GX Developer
When connecting to QCPU (A mode)
When connecting to QCPU (A mode), set the PLC type
to "A4UCPU" or "QCPU (A mode)" on GX Works3, GX
Works2, GX Developer.
When connecting the GOT and PC with RS-
232
The [Transmission speed] setting in [PC side I/F Serial
setting] in GX Works3, GX Works2, GX Developer must
be within the range supported by the connected CPU.
CPU connected
9600bps, 19200bps, 38400bps,
57600bps, 115200bps
9600bps, 19200bps, 38400bps
9600, 19200bps
9600bps
When [monitor conditions] have been set on
GX Works3, GX Works2, GX Developer
suspended.
and numerical/ascii inputs.
and displays the message, "315 Device writing error.
Correct device.".
any operation which makes the GOT restart (e.g.
downloading project data, changing utility data).
Doing so may display a system alarm, "402
Communication timeout. Confirm communication
pathway or modules." when the GOT restarts.
When the monitor conditions setting for the PLC CPU
has not been cancelled, reconnect GX Works3, GX
Works2, GX Developer to cancel the setting.(An error
may be output when the monitor conditions setting is
cancelled.)
Developer is set to 30 seconds or more in the monitor
condition settings, the message "402 Communication
timeout. Confirm communication pathway or modules."
may appear.
Set the time check time of GX Works3, GX Works2, GX
Developer to 30 seconds or less.
When exiting GX Works3, GX Works2, GX
Developer
For 45 seconds after GX Works3, GX Works2, GX
Developer has been exited, the GOT continues
monitoring at the same speed as when the FA
transparent function is working.
23. FA TRANSPARENT FUNCTION
23.7 Precautions
Transmission speed
23 - 87
17
18
19
20
21
22
23