4.5 MELSECNET/H and MELSECNET/10 Connections
(Network Systems)
This section explains the MELSECNET/H and MELSECNET/10 connections (network systems) that connect the GOT to
the MELSECNET/H and MELSECNET/10 network system.
The following provides an example of connecting the GOT set as a normal station to the MELSECNET/ H network
system.
Network No. 1, Station No. 1
(Control station)
Monitor target
Control
system
(System A)
(1) Connection method
Connect the MELSECNET/H network system to the GOT.
For details, refer to the following.
(2) GT Designer3 setting
Set GT Designer3 as follows.
Setting item
Controller Type
Device setting (Network setting)
Q Redundant Setting
(3) Monitoring target change when system switching occurs in a redundant system
When system switching occurs, the network module station No. 2 changes from the normal station to the sub
control station and takes over the control of the MELSECNET/H network system.
Since the GOT monitors the control system, the monitoring target is automatically changed to the network
module station No. 2.
POINT
POINT
POINT
To monitor the control system without Q redundant setting
When system switching occurs, the network module station No. 2 changes from the normal station to the sub
control station and takes over the control of the MELSECNET/H network system.
Since the GOT monitors the station of the specified station number, the monitoring target cannot be changed to the
station No. 2 in response to the system switching.
As a countermeasure, create a screen to monitor the PLC CPU of the control system by switching the station
numbers between System A and System B using the script function.
4 - 22
4. HOW TO MONITOR REDUNTANT SYSTEM

4.5 MELSECNET/H and MELSECNET/10 Connections (Network Systems)

GOT
MELSECNET/H remote I/O network
9. MELSECNET/H CONNECTION (PLC TO PLC NETWORK)
MELSEC-QnA/Q/QS, MELDAS C6*
Other
4.9 Q Redundant Setting
4.10 Switch the Monitor Target to the Control System Using the Script Function
Network No. 1, Station No. 3 (Normal station)
MELSECNET/H PLC to PLC network
(MELSECNET/H mode or
MELSECNET/10 mode)
Settings
NW No.: Network No. of MELSECNET/H PLC to PLC network
Station No.: Station number of the control system
Network No. 1, Station No. 2
(Normal station)
Standby
system
(System B)