Got Side Settings; Setting Communication Interface (Communication Settings); Communication Detail Settings - Mitsubishi Electric GT1685 Connection Manual

Got1000 series
Table of Contents

Advertisement

5.3 GOT Side Settings

5.3.1
Setting communication
interface (Communication
settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: MITSUBISHI ELECTRIC
• Controller Type: Set the option according to the
Controller Type to be connected.
• I/F: Interface to be used
• Driver: Set either of the following option according
to the Controller Type to be connected.
BUS (Q)
BUS (A/QnA)
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.

5.3.2 Communication detail settings

Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
5 - 32
5. BUS CONNECTION

5.3 GOT Side Settings

3.
4.
Click!
[Controller Setting] from the
5.3.2
Communication detail settings
(1) Bus(Q)
Item
Description
Number of
(Default: 1)
Stages
Slot No.
(Default: 0)
Set the monitor speed of the GOT.
Monitor Speed
This setting is not valid in all systems.
(Default: Normal)
Set the time period for a
Timeout Time
communication to time out.
(Sec.)
(Default: 12)
*1
This range is effective when collecting a large amount of
data (such as logging and recipe function) on other than the
monitor screen.
However, the range may affect the sequence scan time
when connecting to Q00UJ/Q00U/Q01U/Q02UCPU or Q00J/
Q00/Q01CPU.
If you want to avoid the influence on the sequence scan time,
do not set [High].
(This setting hardly affects QCPUs other than the above.)
*2
Set this range if you want to avoid the influence on the
sequence scan time further than the [Normal] setting when
connecting to Q00UJ/Q00U/Q01U/Q02UCPU or Q00J/Q00/
Q01CPU.
However, the monitor speed may be reduced.
(2) Bus(A/QnA)
Item
Description
Number of
(Default: 1)
Stages
Slot No.
(Default: 0)
Set the time period for a
Timeout Time
communication to time out.
(Sec.)
(Default: 3)
Range
1 to 7
0 to 9
*1
High
/Normal/
*2
Low
12 to 90
Range
1 to 7
0 to 7
3 to 90

Hide quick links:

Advertisement

Table of Contents
loading