Mitsubishi Electric GT1685 Connection Manual page 452

Got1000 series
Table of Contents

Advertisement

*1
Transmission speed settings
The following lists the transmission speed settings of the CC-
Link communication.
Set value
0
1
2
3
4
A
B
C
D
E
For details of the hardware test, refer to the following
manual.
CC-Link System Master/Local Module User's
Manual for CC-Link module to be used
13 - 12
13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
13.3 GOT Side Settings
Description
Online: 156kbps
Online: 625kbps
Online: 2.5Mbps
Online: 5Mbps
Online: 10Mbps
Hardware test: 156kbps
Hardware test: 625kbps
Hardware test: 2.5Mbps
Hardware test: 5Mbps
Hardware test: 10Mbps
(2) CC-Link(ID)
Item
Description
Set the number of retries to be
performed when a communication
timeout occurs.
Retry
When no response is received after
retries, a communication times out.
(Default: 3times)
Set the time period for a communication
Timeout Time
to time out.
(Default: 3sec)
POINT
POINT
POINT
(1) Communication interface setting by Utility
The communication interface setting can be
changed on the Utility's [Communication Settings]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
GT
User's Manual
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
Range
0 to 5times
3 to 90sec

Hide quick links:

Advertisement

Table of Contents
loading