Connecting Freqrol-D700 Series - Mitsubishi Electric GT1685 Connection Manual

Got1000 series
Table of Contents

Advertisement

15.5.7 Connecting FREQROL-D700 series

Communication settings
Make the communication settings of the inverter.
Be sure to perform the inverter reset after updating each parameter.
(1) Communication port and corresponding parameters
GOT connection
destination
PU connector
(2) Communication settings of inverter
Set the following parameters using the PU (parameter unit). Set Pr.160 (User group read selection) to 0 [The
simple mode and extended parameters can be displayed] before making the parameter settings.
Do not change these parameters, even though they can be monitored from the GOT. If they are changed,
communication with the GOT is disabled.
Setting item
PU communication station number
PU communication speed
PU communication stop bit length*2
PU communication parity check
Number of PU communication retries
PU communication check time interval
PU communication wait time setting
PU communication CR/LF selection
Protocol selection
Operation mode selection
Communication startup mode selection
Communication EEPROM write selection
*1
Setting items are parameter names described in the manual of FREQROL-D700 series.
*2
Settings on the GOT can be changed.
When changing the settings on the GOT, be sure to change the parameters on the inverter to correspond with the GOT settings.
*3
Inverter default values (No need to change)
15 - 40
15. INVERTER CONNECTION
15.5 FREQROL Series Inverter Side Settings
Parameters corresponding to inverter
Pr.79, Pr.117 to Pr.124, Pr.340, Pr.342, Pr.549
*1
Parameter No.
*2
*2
Set value
Pr.117
0 to 31
*3
Pr.118
192
Pr.119
10
Pr.120
1
Pr.121
9999
Pr.122
9999
Pr.123
0
*3
Pr.124
1
*3
Pr.549
0
*3
Pr.79
0
Pr.340
1
*3
Pr.342
0
Contents of setting
15.5.14 Station number
setting
19200bps
Data length: 7bit
Stop bit length: 1bit
Odd
The inverter will not come to an
alarm stop.
Communication check
suspension
0ms
With CR, without LF
Mitsubishi Electric inverter
protocol
PU operation mode
Network operation mode.
Written to RAM and EEPROM