To connect the GOT with the Ethernet module (Q Series) in
the one-on-one relationship using a cross cable, set
[Timeout Time] to 6sec. or longer.
*2
Click the [Setting] button and perform the setting in the [GOT
IP Address Setting] screen.
*3
Each of [GOT PLC No.] set in the communication detail
setting and [PLC No.] set in the Ethernet setting must be set
to different station numbers.
8.3.3 Ethernet setting
*4
When connecting to the QCPU, LCPU, do not set [5009] for
the port No. Otherwise, monitoring becomes unavailable.
8 - 18
8. ETHERNET CONNECTION
8.3 GOT Side Settings
GT15
Description
Item
Set the network No. of the GOT.
GOT NET No.
(Default: 1)
Set the station No. of the GOT.
*2
GOT PLC No.
(Default: 1)
GOT
Set the IP address of the GOT.
IP address
(Default: 192.168.0.18)
Set the subnet mask for the sub
network.(Only for connection via router)
Subnet
If the sub network is not used, the
Mask
default value is set.
(Default: 255.255.255.0)
Set the router address of the default
gateway where the GOT is
Default
connected.(Only for connection via
Gateway
router)
(Default: 0.0.0.0)
Ethernet
Set the GOT port No. for Ethernet
Download
download.
Port No.
(Default: 5014)
Set the GOT port No. for the connection
with the Ethernet module.
GOT
• For Ethernet (MELSEC), Q17nNC,
Communication
and CRnD-700
*3
(Default: 5001)
Port No.
• For Ethernet(FX), Gateway
(Default: 5019)
Set the number of retries to be
performed when a communication
timeout occurs.
Retry
When receiving no response after
retries, the communication times out.
(Default: 3times)
Specify the time period from the GOT
startup until GOT starts the
Startup Time
communication with the PLC CPU.
(Default: 3sec)
Set the time period for a communication
Timeout Time
to time out.
*1
(Default: 3sec)
Set the delay time for reducing the load
Delay
of the network/destination PLC.
Time
(Default: 0ms)
*1
To connect the GOT with the Ethernet module (Q Series) in
the one-on-one relationship using a cross cable, set
[Timeout Time] to 6sec. or longer.
*2
Each of [GOT PLC No.] set in the communication detail
setting and [PLC No.] set in the Ethernet setting must be set
to different station numbers.
8.3.3 Ethernet setting
*3
When connecting to the QCPU, LCPU, do not set [5009] for
the port No. Otherwise, monitoring becomes unavailable.
Range
1 to 239
1 to 64
0.0.0.0 to
255.255.255.255
0.0.0.0 to
255.255.255.255
0.0.0.0 to
255.255.255.255
1024 to 5010,
5014 to 65534
(Except for 5011, 5012,
5013 and 49153)
1024 to 5010,
5014 to 65534
(Except for 5011, 5012,
5013 and 49153)
0 to 5times
3 to 255sec
3 to 90sec
0 to 10000
(
10ms)