FusionModule2000 Smart Modular Data Center
Installation Guide
Figure 10-21 Securing sealing plates
Step 3 Place the side sealing plate with the side with dents upward, and snap the side sealing plate
into the front and rear sealing plates, as shown by (2) in
Side sealing plates need to be installed only for end cabinets and cabinets at both sides of a
column, but not middle cabinets.
----End

10.5 Installing End Doors

Table 10-4 Pre-installation checklist
No.
1
2
3
Issue 02 (2018-03-31)
Check Item
The cabinets have been leveled. If there is a height
deviation, its absolute value does not exceed 3 mm.
The distance between cabinet doors inside the dual-row
aisle containment is 1200 mm (± 3 mm).
The distance between cabinet doors and sealing plates
inside the single-row aisle containment is 1225 mm (± 3
mm).
The cabinets in both rows at the ends of the dual-row aisle
containment are placed with a front-backward deviation no
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
10 Installing the Aisle Containment
Figure
10-21.
Result
□ Passed □ Failed