Figure 10-48 Door boxes in place
Step 7 Adjust the gaps.
After the door boxes are placed, the gaps between the door boxes and the posts may be
uneven and need to be adjusted, as shown in
Table 10-8 Door box placement faults
Fault Type
Door box tilted with a
V-shaped gap
Door box tilted with a
Λ-shaped gap
1.
Issue 02 (2018-03-31)
Figure 10-49
shows a tilted door box. Turn the M6 door box screw in the leveling corner
piece furthest from the door frame clockwise to lift the door box until the V-shaped gap
disappears, as shown by (1) in
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Figure 10-49
Possible Cause
The top front and rear of the
cabinet are not on the same
level. Usually the front is
higher than the rear.
The top front and rear of the
cabinet are not on the same
level. Usually the front is
lower than the rear.
Figure
10-50.
10 Installing the Aisle Containment
and
Figure
10-51.
Measure
For details about the
adjusting method, see
7.1.
For details about the
adjusting method, see
7.2.
Step
Step
137