Installing A Smart Eth Gateway - Huawei FusionModule2000 Installation Manual

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Installation Guide
Scenario
Rack environment unit deployed
Figure 15-69 Layout of smart ETH gateways in scenario 3

15.5.3 Installing a Smart ETH Gateway

Preparations
Tool: Phillips screwdriver
Materials: smart ETH gateway and accessories
Procedure
Step 1 Use two M4x10 screw assemblies to secure the guide rail for the smart ETH gateway to the
cable trough, as shown in
Issue 02 (2018-03-31)
When the smart module is 4 meters long or less, no multi-functional sensor is deployed in the
network cabinet.
When the smart module is longer than 7 meters, deploy one multi-functional sensor in the module
aisle (one more control skylight is required). Connect the multi-functional sensor to any smart ETH
gateway in the middle.
Figure
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Rules for Deploying Smart ETH
Gateways
Deploy two smart ETH gateways for each
end cabinet and one smart ETH gateway for
every three cabinets among other cabinets in
the smart module, as shown in
15-70.
15 Installing Monitoring Devices
Figure
15-69.
228