Interconnect the male and female connectors of lights in the same group.
For lights in the same group, only the light in either end needs to be connected to the
power supply.
Figure 12-5 Cable connections to lights in the same group
(1) AC actuator
1.
(A) Light
2.
Issue 02 (2018-03-31)
Connect lights in series, and connect the light near the AC actuator to the cable delivered
with the light.
Figure 12-6 Cable connections to aisle lights
Cut off the plug at the other end of the cable delivered with the light, strip the insulation
layer for the cut end, and route the cable out of the aisle containment.