Huawei FusionModule2000 Installation Manual page 83

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Installation Guide
Figure 7-6 Securing an adaptive frame
Step 4 Install the rear panel in the same way.
Step 5 Use four M4x10 screw assemblies to secure the top panel to the front and rear panels, as
shown by (1) in
Do not over-tighten the top panel of the adaptive frame. Otherwise, the top panel will be
uneven.
Issue 02 (2018-03-31)
Figure
7-7.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
7 Installing Air Conditioners
74