Figure 10-1 Installing a sealing plate
Step 4 Secure sealing plates to the floor using ST4.8x25 self-drilling tapping screws and washers, as
shown by (2) in
The number of screws used for securing the sealing plate must be the same as the number of
corresponding holes in the lower end of the plate.
Step 5 Install other sealing plates in the same way.
Step 6 Connect adjacent sealing plates using three M6x16 screws with flat washers and nuts, as
shown by (3) in
----End