FusionModule2000 Smart Modular Data Center
Installation Guide
Floating nuts must be installed in mounting holes alternatively on the dehumidifier.
Three floating nuts need to be installed at each side.
Ensure that the floating nuts on both sides are on the same horizontal line.
When installing the dehumidifier, verify that the air intake vent faces the cold aisle (as
shown by A in
Figure
Figure 13-3 Installing a floating nut
Step 4 Secure the dehumidifier to the rack rails using M6 screws and dehumidifier mounting ears.
Figure 13-4 Installing a dehumidifier
Step 5 Connect the dehumidifier drainpipe.
Issue 02 (2018-03-31)
Figure
13-1), and the air exhaust vent faces the hot aisle (as shown by B in
13-1).
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
13 (Optional) Installing Dehumidifiers
173