■4. Enhanced interaction with objects (one-touch ladder jump function)
(1) Interaction with the special function switch
The automatic PLC read or the device automatic search can be executed at startup of the sequence program monitor
(Ladder) or sequence program monitor (R ladder) by the following method. Place a special function switch on a user-
created screen, specify the search file and search device in the special function switch setting, and then touch the
special function switch.
Even a person who is not the operator familiar with the equipment inside can trace the source of the equipment error
without fail by simple operations, reducing time to stop the error.
Example) Coil searching by touching a special function switch
(User-created screen)
Operation flow screen
Home position
Lifter down
Lifter down
Hand open
Hand close
Lifter up
Lifter up
Forward
Back
Touch the special function button of error process
Special function switch setting
Ladder Search Device: M53
Ladder Search Mode: Coil
(2) Interaction with the alarm display (user) or simple alarm display
The sequence program monitor (Ladder) or the sequence program monitor (R ladder) can be started to search for a
device having an alarm by the following method. Select an alarm in the alarm display, and touch a key code switch
(Display ladder (Ladder Editor)).
(User-created screen)
Occurred
09/8/1 14:46:49
09/8/1 13:30:14
Display Ladder
(Ladder Editor)
Select an alarm and touch the key code switch.
Key code switch setting
Code setting:
FFBD : Sequence program monitor (ladder)
FFBA : Sequence program monitor (R ladder)
The sequence program
monitor (ladder) starts
and searches for coil
"M53" automatically.
Comment
Temp. error
Fuse error
The sequence program
monitor (ladder) starts
and searches for the
device of alarm
automatically.
(Ladder monitor screen)
Lifter lower
Hand close
end
X13
X13
M52
M52
M54
M54
M53
M53
Lifter upper
Lifter up
end
X10
X10
M53
M53
M55
M55
M54
M54
"Forward operation M54" was not turned
on since the lifter upper-end sensor (X10)
was not turned on.
(Ladder monitor screen)
M12
M12
X13
X13
The search result is displayed.
4.1 Features
4
M53
M53
Lifter up
M54
M54
Forward
Y43
Y44
Y45
Y46
4 - 3