Composition Of Pc Information Monitor Screen And Key Functions - Mitsubishi Electric GOT2000 Series User Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

3) [Enter] key
Moves the cursor when the cursor is in the CH No. input area, network No. input area, or station No. input area.
When the cursor is in the CPU No. input area and settings for the CH No., network No., and station No. are
completed, the communication setting window closes and the PLC read screen appears.
4) [Del] key
Deletes an input value or character.
5) [AC] key
Deletes all the input values and characters.
8.4.3

Composition of PC Information monitor screen and key functions

This section describes the structure of the PC Information monitor screen and the functions of the keys displayed on screen.
The PC Information monitor screen is displayed by specifying the RCPU, QCPU (Q mode), QSCPU, or LCPU on the system
configuration screen.
The GOT displays the PC Information monitor screen only when using the following controllers.
• RCPU
• QCPU (Q mode)
• QSCPU
• LCPU
■1. When using the RCPU, QCPU (Q mode), or LCPU
(1) PC information monitor screen
(a)
Displayed contents
1) Monitored station display
Displays the channel number, network number and station number of the monitored station.
2) Touch key
Displays the keys that are used for the operation on the PC information monitor screen.
3) [CPU Working State]
Displays the operating status of the PLC CPU.
4) Error display
Displays the currently occurring errors.
When using the LCPU, touch the error cause to display the error detail screen.
8 - 14
8.4 Operation of Each Intelligent Module Monitor Screen
1)
3)
4)
(2) Error details screen
5)
2)
2)
2)