6.2
Reset the inverter by performing any of the following operations. Note that the accumulated heat value of the electronic thermal
relay function and the number of retries are cleared (erased) by resetting the inverter.
The inverter recovers about 1 second after the reset is released.
• On the operation panel, press
is activated. (Refer to
• Switch the power OFF once, then switch it ON again.
• Turn ON the Reset (RES) signal for 0.1 second or more. (If the RES signal is kept ON, "Err" appears (blinks) to indicate
that the inverter is in a reset status.)
NOTE
• OFF status of the start signal must be confirmed before resetting the inverter fault. Resetting an inverter fault with the start
signal ON restarts the motor suddenly.
Downloaded from
ManualsNet.com

Reset method for the protective functions

to reset the inverter. (This operation is valid only when a protective function for a fault
page 785
of the Instruction Manual for faults.))
ON
OFF
Inverter
RES
SD
search engine
6. PROTECTIVE FUNCTIONS
6.2 Reset method for the protective functions