1.
After completion of deceleration stop, turn OFF the STF or STR signal.
2.
Press
• The inverter can be restarted by performing the reset operation (by turning OFF and ON the power or inputting the RES
signal).
NOTE
• Even when Pr.250 Stop selection ≠ "9999" is set and coasting stop is selected, using the PU stop function in the External
operation mode does not provide coasting stop but deceleration stop.
Reset limit (P.E107)
• Setting P.E107 = "1" or Pr.75 = any of "100 to 103, 114 to 117, 1100 to 1103, or 1114 to 1117" will make the inverter to
refuse any reset operation (RES signal input, etc.) for 3 minutes after the first activation of an electronic thermal O/L relay
or protective function (E.THM, E.THT, E.OC[]).
• The reset limit function is available with the FR-A820-03800(75K) or higher and the FR-A840-02160(75K) or higher.
NOTE
• Resetting the inverter power (turning OFF the control power) clears the accumulated thermal value.
• When the retry function is set enabled (Pr.67 Number of retries at fault occurrence ≠ "0"), the reset limit function is disabled.
CAUTION
• Do not perform a reset while a start signal is being input. Doing so will cause a sudden start of the motor, which
is dangerous.
Parameters referred to
Pr.67 Number of retries at fault
Pr.79 Operation mode
Pr.250 Stop
selectionpage 722
Pr.551 PU mode operation command source
5.7.3
You can switch the display language of the parameter unit (FR-PU07) to another.
Pr.
145
PU display language
E103
selection
Downloaded from
ManualsNet.com
("
" is cleared).
EXT
Speed
Operation
panel
STF
ON
(STR) OFF
occurrencepage 426
selectionpage 389
selectionpage 400
PU display language selection
Name
Initial value
—
search engine
Key
Key
Stop/restart example for External operation
Setting range
0
1
2
3
4
5
6
7
Time
Description
Japanese
English
German
French
Spanish
Italian
Swedish
Finnish
5.7 (E) Environment setting parameters
1
2
3
4
5
6
7
8
9
10
339
5. PARAMETERS