Mitsubishi Electric FR-A800 Series Instruction Manual page 369

Hide thumbs Also See for FR-A800 Series:
Table of Contents

Advertisement

For the acceleration time at automatic restart after instantaneous power failure, refer to Pr.611 Acceleration time at a restart
(page
628,
page
635).
Pr.
Name
Acceleration/
20
deceleration
F000
reference
frequency
Acceleration/
21
deceleration time
F001
increments
16
Jog acceleration/
F002
deceleration time
611
Acceleration time
F003
at a restart
7
Acceleration time
F010
8
Deceleration time
F011
Second
44
acceleration/
F020
deceleration time
45
Second
F021
deceleration time
Acceleration/
147
deceleration time
F022
switching
frequency
Third
110
acceleration/
F030
deceleration time
111
Third deceleration
F031
time
Acceleration time
791
in low-speed
F070
range
Deceleration time
792
in low-speed
F071
range
1103
Deceleration time
F040
at emergency stop
Emergency stop
1349
operation
G264
selection
*1
The initial value for the FR-A820-00490(7.5K) or lower and FR-A840-00250(7.5K) or lower.
*2
Initial value for the FR-A820-00630(11K) or higher and FR-A840-00310(11K) and higher.
368
5. PARAMETERS
5.8 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
Downloaded from
ManualsNet.com
Initial value
Setting range
FM
CA
60 Hz
50 Hz 1 to 590 Hz
0
0
1
0.5 s
0 to 3600 s
0 to 3600 s
9999
9999
*1
5s
0 to 3600 s
*2
15s
*1
5s
0 to 3600 s
*2
15s
5 s
0 to 3600 s
0 to 3600 s
9999
9999
0 to 590 Hz
9999
9999
0 to 3600 s
9999
9999
0 to 3600 s
9999
9999
0 to 3600 s
9999
9999
0 to 3600 s
9999
9999
5 s
0 to 3600 s
0
1
0
10
11
search engine
Description
Set the frequency that is the basis of acceleration/deceleration time.
As acceleration/deceleration time, set the time required to change
the frequency from a stop status (0 Hz) to the frequency set in Pr.20
and vice versa.
Increment: 0.1 s
Increment: 0.01 s
Set the acceleration/deceleration time for JOG operation (from stop
status to Pr.20). Refer to
page
410.
Set the acceleration time for restart (from stop status to Pr.20).
Standard acceleration time (for example, Pr.7) is applied as the
acceleration time at restart. Refer to
Set the motor acceleration time (time required to change the
frequency from a stop status (0 Hz) to the frequency set in Pr.20).
Set the motor deceleration time (from Pr.20 to stop status).
Set the acceleration/deceleration time used while the RT signal is
ON.
Set the deceleration time used while the RT signal is ON.
The acceleration time applies to the deceleration time.
Set the frequency where the acceleration/deceleration time
switches to the time set in Pr.44 and Pr.45.
Function disabled.
Set the acceleration/deceleration time when the X9 signal is ON.
Third acceleration/deceleration is disabled.
Set the deceleration time when the X9 signal is ON.
The acceleration time applies to the deceleration time.
Set the acceleration time in a low-speed range (less than 1/10 of the
rated motor frequency).
The acceleration time set in Pr.7 is applied. (While the RT signal or
the X9 signal is ON, the second or third function is enabled.)
Set the deceleration time in a low-speed range (less than 1/10 of the
rated motor frequency).
The deceleration time set in Pr.8 is applied. (While the RT signal or
the X9 signal is ON, the second or third function is enabled.)
Set the motor deceleration time at a deceleration by turning ON the
X92 signal.
Droop control enabled.
Droop control enabled.
Droop control disabled.
Droop control disabled.
Select the increment for
the acceleration/
deceleration time setting.
page
628,
page
635.
Speed loop integration
enabled.
Speed loop integration
disabled.
Speed loop integration
enabled.
Speed loop integration
disabled.