Mitsubishi Electric FR-A800 Series Instruction Manual page 76

Hide thumbs Also See for FR-A800 Series:
Table of Contents

Advertisement

2.
Crimp the terminals on the wire.
Insert the wire into a crimp terminal, making sure that 0 to 0.5 mm of the wire protrudes from the end of the sleeve.
Check the condition of the crimp terminals after crimping. Do not use the crimp terminals of which the crimping is
inappropriate, or the face is damaged.
Crimp terminals commercially available (as of October 2020)
• Phoenix Contact Co., Ltd.
Wire gauge
2
(mm
)
0.3
0.5
0.75
1
1.25, 1.5
0.75 (two-wire product)
*1
A ferrule terminal with an insulation sleeve compatible with the MTW wire which has a thick wire insulation.
*2
Applicable for terminals A1, B1, C1, A2, B2, C2.
• NICHIFU Co., Ltd.
Wire gauge
2
(mm
)
0.3 to 0.75
3.
Insert the wire into the terminal block.
NOTE
• When using stranded wires without a blade terminal, twist enough to avoid short circuit with a nearby terminals or wires.
• Place the flathead screwdriver vertical to the open/close button. In case the blade tip slips, it may cause an inverter damage
or injury.
Downloaded from
ManualsNet.com
With insulation sleeve
AI 0,34-10TQ
AI 0,5-10WH
AI 0,75-10GY
AI 1-10RD
AI 1, 5-10BK
AI-TWIN 2×0,75-10GY
Blade terminal part
No.
BT 0.75-11
search engine
Damaged
Ferrule part No.
Without insulation sleeve
A 0,75-10
A 1-10
A 1, 5-10
Crimping tool model
Insulation cap part No.
VC 0.75
NH 69
When using single wire or stranded wire without crimp terminal,
push an open/close button all the way down with a flathead
screwdriver, and insert the wire.
Wires are not inserted
Crumpled tip
into the sleeve
Crimping tool
*1
For UL wire
AI 0,5-10WH-GB
AI 0,75-10GY-GB
CRIMPFOX 6
AI 1-10RD/1000GB
*2
AI 1,5-10BK/1000GB
No.
Open/close button
Flathead screwdriver
2. INSTALLATION AND WIRING
1
2
Unstranded
wires
3
4
model No.
5
6
7
8
9
10
75
2.6 Control circuit

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents