When the Advanced magnetic flux vector control, Real sensorless vector control, Vector control, or PM sensorless vector
control is selected, the motor constant necessary for control (SF-PR, SF-JR, SF-HR, SF-JRCA, SF-HRCA, SF-V5RU (1500 r/
min series), MM-CF, etc.) is also selected at the same time.
Pr.
71
Applied motor
C100
450
Second applied motor
C200
Setting the applied motor
• Refer to the following list and set the parameters according to the applied motor.
Pr.71
Pr.450
0 (Pr.71 initial
value)
1
2
—
20
30
40
50
70
*1
330
8090
9090
Downloaded from
ManualsNet.com
Name
Initial value
0
9999
Motor
Standard motor (such as SF-JR)
Constant-torque motor (SFJRCA,
etc.)
SF-V5RU (other than the 1500 r/
min series)
Standard motor (such as SF-JR)
Adjustable 5 points V/F (refer to
page
713)
Mitsubishi Electric standard motor
(SF-JR 4P 1.5kW or lower)
Vector control dedicated motor
SF-V5RU (1500 r/min series)
SF-THY
Mitsubishi Electric high-efficiency
motor SF-HR
Mitsubishi Electric constant-
torque motor SF-HRCA
Mitsubishi Electric high-
performance energy-saving motor
SF-PR
IPM motor MM-CF
IPM motor (other than MM-CF)
SPM motor
search engine
Setting range
0 to 6, 13 to 16, 20, 23, 24, 30,
33, 34, 40, 43, 44, 50, 53, 54, 70,
73, 74, 330, 333, 334, 8090,
8093, 8094, 9090, 9093, 9094
0, 1, 3 to 6, 13 to 16, 20, 23, 24,
30, 33, 34, 40, 43, 44, 50, 53, 54,
70, 73, 74, 330, 333, 334, 8090,
8093, 8094, 9090, 9093, 9094
9999
Motor constant value range when performing
offline auto tuning (increment)
Pr.82 (Pr.455) and Pr.859 (Pr.860)
*2
• 0 to 500 A, 9999 (0.01 A)
*3
• 0 to 3600 A, 9999 (0.1 A)
Pr.90 (Pr.458), Pr.91 (Pr.459)
*2
• 0 to 50 Ω, 9999 (0.001 Ω)
*3
• 0 to 400 mΩ, 9999 (0.01 mΩ)
Pr.92 (Pr.460), Pr.93 (Pr.461) (Induction motor)
*2
• 0 to 6000 mH, 9999 (0.1 mH)
*3
• 0 to 400 mH, 9999 (0.1 mH)
Pr.92 (Pr.460), Pr.93 (Pr.461) (PM motor)
*2
• 0 to 500 mH, 9999 (0.01 mH)
*3
• 0 to 50 mH, 9999 (0.001 mH)
Pr.94 (Pr.462)
*2
• 0 to 100%, 9999 (0.1%)
*3
• 0 to 100%, 9999 (0.01%)
Pr.706 (Pr.738)
• 0 to 5000 mV (rad/s), 9999 (0.1 mV/(rad/s))
Description
By selecting a motor, the thermal characteristic
and motor constant of each motor are set.
Set this parameter when using the second motor
(the same specifications as Pr.71).
The function is disabled.
Electronic thermal O/L relay
function
Constant-
Standard
○
○
○
○
○
○
○
○
○
○
5. PARAMETERS
5.13 (C) Motor constant parameters
1
2
3
4
5
PM
6
torque
7
8
9
10
○
529