Pulse Train Output To Announce Cumulative Output Energy - Mitsubishi Electric FR-A800 Series Instruction Manual

Hide thumbs Also See for FR-A800 Series:
Table of Contents

Advertisement

Pr.
76
Fault code output selection
M510
• Fault codes can be output to the output terminals by setting Pr.76 Fault code output selection = "1 or 2".
• When the setting is "2", a fault code is only output when a fault occurs. In normal operation the terminal outputs the signal
assigned in Pr.191 to Pr.194 (Output terminal function selection).
• The fault codes that can be output are shown in the following table. (0: Output transistor OFF, 1: Output transistor ON)
Operation panel
indication (FR-DU08)
*1
Normal
E.OC1
E.OC2
E.OC3
E.OV1 to E.OV3
E.THM
E.THT
E.IPF
E.UVT
E.FIN
E.BE
E. GF
E.OHT
E.OLT
E.OPT,
E.OP1 to E.OP3
Terminals other than the
above
*1
When Pr.76 = "2", the terminal outputs the signal assigned by Pr.191 to Pr.194.
NOTE
• If an error occurs while Pr.76 ≠ "0", the output terminals SU, IPF, OL, and FU output the signals in the table above regardless
of the settings in Pr.191 to Pr.194 (Output terminal function selection). Take caution when controlling the inverter with the
output signals set by Pr.191 to Pr.194.
Parameters referred to
Pr.190 to Pr.196 (Output terminal function
5.11.13 Pulse train output to announce cumulative output
Every time when the output energy cumulated from the time at power ON or at an inverter reset or when the setting of Pr.799
Pulse increment setting for output power has been changed increments by the set value, the Pulse train output of output
power (Y79) signal is output in pulses.
Pr.
799
Pulse increment setting for
M520
output power
 Pulse increment setting for output power (Y79 signal, Pr.799)
• Every time when the output energy cumulated from the time at power ON or at an inverter reset increments by the set value
of Pr.799 Pulse increment setting for output power, the Pulse train output of output power (Y79) signal is output in
pulses.
Downloaded from
ManualsNet.com
Name
Initial value
0
SU
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
selection)page 473
energy
Name
Initial value
1 kWh
search engine
Setting range
0
Without fault code output
1
With fault code output
2
Fault code is output only when a fault occurs
Output terminal operation
IPF
OL
0
0
0
0
0
1
0
1
1
0
1
0
1
1
1
1
0
0
0
0
0
1
0
1
1
0
1
0
1
1
1
1
Setting range
0.1 kWh, 1 kWh,
The Pulse train output of output power (Y79) signal is output
10 kWh, 100 kWh,
in pulses every time when the output energy increments by
1000 kWh
the set amount of energy (kWh).
Description
Fault code
FU
0
0
1
1
0
2
1
3
0
4
1
5
0
6
1
7
0
8
1
9
0
A
1
B
0
C
1
D
0
E
1
F
Description
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
1
2
3
4
5
6
7
8
9
10
493

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents