 PID action
PID action is a combination of PI and PD action, which enables control that incorporates the respective strengths of these
actions.
Set point
Measured value
P action
I action
D action
PID action
(Note) PID action is the result of all P, I and D actions being added together.
 Reverse action
When deviation X = (set point - measured value) is a plus value, the manipulated amount (output frequency) is increased, and
when the deviation is a minus value, the manipulated amount is decreased.
 Forward action
When deviation X = (set point - measured value) is a minus value, the manipulated amount (output frequency) is increased,
and when the deviation is a plus value, the manipulated amount is decreased.
Relationship between deviation and manipulated amount (output frequency)
PID action setting
Reverse action
Forward action