Mitsubishi Electric FR-A800 Series Instruction Manual page 436

Hide thumbs Also See for FR-A800 Series:
Table of Contents

Advertisement

 Adjusting the stall prevention operation signal and output timing (OL
signal, Pr.157)
• If the output current exceeds the stall prevention operation level and stall prevention is activated, Overload warning (OL)
signal turns ON for 100 ms or more. The output signal turns OFF when the output current falls to the stall prevention
operation level or less.
• Pr.157 OL signal output timer can be used to set whether to output the OL signal immediately, or whether to output it
after a certain time period has elapsed.
• This function also operates during regeneration avoidance operation "
Pr.157 setting
0 (initial value)
0.1 to 25
9999
Overload state
(OL operation)
OL output signal
NOTE
• OL signal is assigned to the terminal OL in the initial status. The OL signal can be assigned to other terminals by setting "3
(positive logic) or 103 (negative logic)" in any of Pr.190 to Pr.196 (Output terminal function selection).
• If the stall prevention operation has lowered the output frequency to 0.5 Hz and kept the level for 3 seconds, the stall prevention
stop (E.OLT) is activated to shut off the inverter output.
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
 Setting for stall prevention operation in the high-frequency range (Pr.22,
Pr.23, Pr.66)
Pr.22
• When operating at the rated motor frequency or higher, acceleration may not be made because the motor current does
not increase. Also, when operating in the high-frequency range, the current flowing to the locked motor becomes less than
the rated output current of the inverter; and even if the motor is stopped, the protective function does not operate (OL). In
a case like this, the stall prevention level can be reduced in the high-frequency range to improve the motor's operating
characteristics. This is useful when operating up to the high speed range, such as when using a centrifuge. Normally, set
Pr.66 Stall prevention operation reduction starting frequency to 60 Hz, and Pr.23 Stall prevention operation level
compensation factor at double speed to 100%.
• Calculation formula for stall prevention operation level
Stall prevention operation level (%)
in the high-frequency range
Where,
A =
• When Pr.23 = "9999" (initial value), the stall prevention operation level is constant at the Pr.22 level up to 590 Hz.
Downloaded from
ManualsNet.com
Description
Output immediately.
Output after the set time (s).
Not output.
Pr.157 Set time(s)
Always at the Pr.22 level
when Pr.23 = "9999"
Stall prevention operation level
as set in Pr.23
400Hz
Pr.66
Output frequency (Hz)
= A + B × [
Pr.66 (Hz) × Pr.22 (%)
, B =
Output frequency (Hz)
search engine
Setting example (Pr.22 = 120%, Pr.23 = 100%, Pr.66 = 60Hz)
120
72
36
24
18
Pr.22 - A
Pr.23 - 100
] × [
]
Pr.22 - B
100
Pr.66 (Hz) × Pr.22 (%)
400 Hz
" (overvoltage stall).
0
60
100
200
300
Output frequency (Hz)
5.10 (H) Protective function parameter
1
2
3
4
5
6
7
8
9
10
400
435
5. PARAMETERS

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents