Mitsubishi Electric FR-A800 Series Instruction Manual page 452

Hide thumbs Also See for FR-A800 Series:
Table of Contents

Advertisement

Monitor item
32-bit cumulative
energy (lower 16 bits)
32-bit cumulative
energy (upper 16 bits)
32-bit cumulative
energy (lower 16 bits)
32-bit cumulative
energy (upper 16 bits)
Remote output value
1
Remote output value
2
Remote output value
3
Remote output value
4
PID manipulated
amount
Second PID set point 0.1%
Second PID
measured value
Second PID deviation 0.1%
Second PID
measured value 2
Second PID
manipulated amount
Dancer main set
speed
Control circuit
temperature
*1
Indication with a minus sign is not possible via RS-485 or MODBUS RTU communication.
*2
To monitor the item on the LCD operation panel (FR-LU08) or the parameter unit (FR-PU07) in the monitor mode, use Pr.774 to Pr.776 or the
monitor function of the FR-LU08 or the FR-PU07 for setting.
*3
The cumulative energization time and actual operation time are accumulated from 0 to 65535 hours, then cleared, and accumulated again from 0.
*4
The actual operation time does not increase if the cumulative running time before power OFF is less than an hour.
*5
On the parameter unit (FR-PU07), the unit "kW" is displayed.
*6
The increment differs according to the inverter capacity. (Increment left of a slash for FR-A820-03160(55K) or lower, FR-A840-01800(55K) or
lower. Increment right of a slash for FR-A820-03800(75K) or higher, FR-A840-02160(75K) or higher.)
*7
Since each readout of the output voltage and output current displayed on the operation panel (FR-DU08) is a four-digit number, a value of more
than 9999 is displayed as "----".
*8
The setting is available for the standard model.
*9
The inverter regards the output current which is less than the specified current level (5% of the rated inverter current) as 0 A. Therefore, each
readout of an output current and output power may show "0" if a too small-capacity motor is used as contrasted with the inverter capacity and the
output current falls below the specified value.
*10 The displayed item can be changed to the pulse after the electronic gear is set by using Pr.430 Pulse monitor selection. (Refer to
*11 Monitoring is available when the compatible plug-in option or control terminal option is installed.
*12 The details of bits for the input terminal status are as follows. (1: ON state, 0: OFF state of a terminal on the inverter. "—" denotes an indefinite
(null) value.)
b15
S1
*13 The details of bits for the output terminal status are as follows. (1: ON state, 0: OFF state of a terminal on the inverter. "—" denotes an indefinite
(null) value.)
b15
-
Downloaded from
ManualsNet.com
Increment
Pr.
RS-485
and unit
setting
1 kWh
H4D
1 kWh
H4E
0.01 kWh/0.1
H4F
*6
kWh
0.01 kWh/0.1
H50
*6
kWh
0.1%
87
H57
0.1%
88
H58
0.1%
89
H59
0.1%
90
H5A
0.1%
91
H5B
92
H5C
0.1%
93
H5D
94
H5E
0.1%
95
H5F
0.1%
96
H60
0.01 Hz.
97
H61
1°C
98
H62
S2
-
-
CS
-
-
-
-
search engine
Negative
MODBUS
indication
RTU
*1
(-)
40277
The upper or lower 16 bits of the 32-bit cumulative
energy is displayed on each indication.
40278
It is monitored via RS-485 communication or other
communication with a communication option installed.
40279
(To find the monitor codes for each communication
option, refer to the Instruction Manual of each
communication option.)
40280
40287
40288
Each setting value of Pr.656 to Pr.659 (Analog remote
output 1 to 4) is displayed. (Refer to
40289
40290
The PID control manipulated amount is displayed. (Refer
40291
to
40292
The set point, measured value, or deviation is displayed
40293
during the second PID control operation. (Refer to
610.)
40294
The PID measured value is displayed while the second
PID control is enabled (Pr.753 ≠ "0"), even if PID control
40295
operating conditions are not satisfied. (Refer to
610.)
The second PID control manipulated amount is
40296
displayed. (Refer to
The set speed for main speed during the dancer control
40297
operation is displayed.
The temperature of the control circuit board is displayed.
(Refer to
40298
When negative number not displayed: 0 to 100°C
When negative number displayed: -20 to 100°C
STP
RES
MRS
JOG
(STOP)
-
-
-
So (SO)
ABC2
Description
page
610.)
page
610.)
page
494.)
RH
RM
RL
RT
ABC1
FU
OL
5.11 (M) Item and output signal for monitoring
1
2
3
4
page
490.)
5
6
page
7
page
8
9
10
page
321.)
b0
AU
STR
STF
b0
IPF
SU
RUN
451
5. PARAMETERS