Mitsubishi Electric FR-A800 Series Instruction Manual page 626

Hide thumbs Also See for FR-A800 Series:
Table of Contents

Advertisement

NOTE
• When Pr.128 is set to "0" or the X14 signal is OFF, regular inverter running not dancer control is performed.
• Dancer control is enabled by turning ON/OFF the bits of terminals assigned the X14 signal by RS-485 communication or over
the network.
• When dancer control is selected, set the PID output suspension function (Pr.575 Output interruption detection time =
"9999").
• When Pr.561 PTC thermistor protection level ≠ "9999", terminal 2 cannot be used for the main speed command. Terminal
2 becomes the PTC thermistor input terminal.
 Selection of set point/measured value input method (Pr.609, Pr.610)
• Select the set point input method by Pr.609 PID set point/deviation input selection and the measured value input
method by Pr.610 PID measured value input selection. Switch the power voltage/current specifications of terminals 2
and 4 by Pr.73 Analog input selection or Pr.267 Terminal 4 input selection to match the specification of the input
device.
• When Pr.133 PID action set point ≠ "9999", Pr.133 is the set point. When the set point is set at Pr.133, the setting
frequency of Pr.902 is equivalent to 0% and the setting frequency of Pr.903 is equivalent to 100%.
Pr.609, Pr.610 settings
1
2
3
4
5
*1
When the same input method has been selected for the set point and measured value at Pr.609 and Pr.610, set point input is invalid. (Inverter
runs at set point 0%)
*2
CC-Link, CC-Link IE Field Network, or LONWORKS communication is available. For details on communication, refer to the Instruction Manual of
each option.
NOTE
• After changing the Pr.73 or Pr.267 settings, check the voltage/current input selection switch. Incorrect setting may cause a
fault, failure or malfunction. (Refer to
• When terminals 2 and 4 are selected for deviation input, perform bias calibration using C3 and C6 to prevent a minus voltage
from being entered as the deviation input signal. Input of a minus voltage might damage devices and the inverter.
• The following shows the relationship between the input values of the analog input terminals, and the set point and
measured value.
Input terminal
Terminal 2
Terminal 1
Terminal 4
*3
Can be changed by Pr.73 and Pr.267 and the voltage/current input switch. (Refer to
Downloaded from
ManualsNet.com
*1
Terminal 1
*1
Terminal 2
*1
Terminal 4
*2
Communication
PLC function
Relationship with analog input
Input
*3
specification
Set point
0 V = 0%
0 to 5 V
5 V = 100%
0 V = 0%
0 to 10 V
10 V = 100%
0 mA = 0%
0 to 20 mA
20 mA = 100%
-5 to 0 V = 0%
0 to ±5 V
+5 V = +100%
-10 to 0 V = 0%
0 to 10 V
+10 V = +100%
0 to 1 V = 0%
0 to 5 V
5 V = 100%
0 to 2 V = 0%
0 to 10 V
10 V = 100%
0 to 4 mA = 0%
0 to 20 mA
20 mA = 100%
search engine
Input method
page 496
for the setting.)
Result
0 V = 0%
5 V = 100%
0 V = 0%
10 V = 100%
0 mA = 0%
20 mA = 100%
-5 to 0 V = 0%
+5 V = +100%
-10 to 0 V = 0%
+10 V = +100%
0 to 1 V = 0%
5 V = 100%
0 to 2 V = 0%
10 V = 100%
0 to 4 mA = 0%
20 mA = 100%
Calibration parameter
Pr.125, C2 to C4
When Pr.128 = "10", Pr.125 setting, C2 to C4.
When Pr.128 ≥ "1000", C12 setting, C2 to C15.
Pr.126, C5 to C7
page
496.)
5. PARAMETERS
5.14 (A) Application parameters
1
2
3
4
5
6
7
8
9
10
625

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents