Mitsubishi Electric FR-A800 Series Instruction Manual page 770

Hide thumbs Also See for FR-A800 Series:
Table of Contents

Advertisement

*1
To the EEPROM, a writing is performed only once after the command Y1022 turns ON.
*2
If the set data is changed at the command Y1022 ON, the change is not applied to the inverter.
 Programming example for the fault record reading
The following program reads the fault records of the station 1 inverter to output to D1.
• Fault history No. 1 and 2 reading instruction code: H74 (hexadecimal)
For the error code, refer to
The reply code (RWr10) to the instruction code execution is set in D2. (Refer to
SB49
SW0B0.0
0
M0
X20
3
M300
7
M301
X1025
9
M302 X1025
16
24
 Programming example for resetting the inverter at an inverter fault
The following program resets the station 1 inverter at an inverter fault.
SB49
SW0B0.0
0
M0 X103A X20
3
Error status flag
7
NOTE
• The inverter reset with the flag RY3A shown above is enabled at an inverter fault only.
• When Pr.349 Communication reset selection/Ready bit status selection = "0 or 100", inverter reset is available
independently of the operation mode.
• When using the instruction code execution request (RY25) with the instruction code (HFD) and data (H9696) to reset the
inverter, set a value other than "0" in Pr.340 Communication startup mode selection or change the operation mode to the
Network operation mode. (For the program example, refer to
Downloaded from
ManualsNet.com
<Timing chart for writing to the RAM>
Y1021
W100
Inverter
set frequency
page
776.
MOV H74
MOV W11 D1
MOV W10 D2
search engine
<Timing chart for writing to the EEPROM>
Y1022
( )
W100
Inverter
set frequency
Apply to the inverter when the command Y1022 turns ON.
M0
Check the data link status of the station 1.
PLS M300
SET M301
Write the fault history No.1 and No.2 read
W110
code (H74) to RWw10.
SET Y1025
Turn ON the instruction code execution request
(RY25).
RST M301
SET M302
Read the fault record (RWr11) and the reply code
(RWr10) to output to D1 and D2 when the instruction
code execution completion (RX25) turns ON.
Turn OFF the instruction code execution request
RST Y1025
(RY25).
RST M302
END
M0
Check the data link status of the station 1.
Turn ON the error reset request flag (RY3A).
Y103A
Turn OFF the error reset request flag (RY3A)
when the error status flag (RX3A) is OFF.
END