Mitsubishi Electric FR-A800 Series Instruction Manual page 763

Hide thumbs Also See for FR-A800 Series:
Table of Contents

Advertisement

Item
Parameter clear
All parameter clear
Inverter reset
Second parameter changing
*1
When "100" is set in Pr.52 Operation panel main monitor selection, set frequency is monitored during a stop and output frequency is monitored
during running.
*2
When position control is selected, the number of pulses is monitored when Pr.430 ≠ "9999".
*3
Write data is in hexadecimal, and only two digits are valid. (The upper two digits are ignored.)
*4
Setting from the remote register (RWw0) is also available.
*5
Turning OFF the power supply while clearing parameters with H5A5A or H55AA returns the communication parameter settings to the initial
settings.
*6
Reading or writing is available when the link parameter extended setting = "1 or 9".
*7
The gain frequency can be also written using Pr.125 (instruction code: H99) or Pr.126 (instruction code: H9A).
NOTE
• When a 32-bit parameter setting or monitored value is read and the read value exceeds HFFFF, the reply data will be HFFFF.
 Torque command / torque limit through CC-Link IE Field Network
communication
• Torque commands can be given or the torque can be limited via CC-Link IE Field Network under Real sensorless vector
control, Vector control, or PM sensorless vector control. The value is used to limit the torque during speed control or
position control, and to give a torque command during torque control. To limit the torque, set Pr.810 = "2". The torque
command / torque limit setting method can be selected using Pr.804 Torque command source selection. (Torque control
cannot be performed with a PM motor.)
• For setting the torque limit parameters, refer to
283.
• Set the torque command value or the torque limit value in RWw2. The RWw2 function is switched according to the Pr.804
and Pr.810 settings and the control mode.
Pr.804 setting Pr.810 setting
2
1, 3, 5, 6
0, 1
0, 4
• Relationship between the Pr.804 setting, the setting range, and the actual torque command / torque limit (when setting is
made from CC-Link IE Field Network communication)
Pr.804 setting
1, 3
600 to 1400 (1% increments)
-32768 to 32767 (two's
5, 6
complement)
*1
The torque limit setting is defined as an absolute value.
762
5. PARAMETERS
5.21 CC-Link IE Field Network (FR-A800-GF)
Downloaded from
ManualsNet.com
Read/
Instruction
write
code
All parameters return to initial values.
Whether to clear communication parameters or not can be selected according to the
data.
• Parameter clear
• All parameter clear
Write
HFC
For details on whether or not to clear parameters, refer to
When clear is performed with H9696 or H9966, communication related parameter
settings also return to the initial values. When resuming the operation, set the
parameters again. Performing a clear will clear the instruction code HEC, HF3, and
HFF settings.
Write
HFD
H9696: Resets the inverter.
Read or write of bias and gain parameters (instruction codes H5E to H61 and HDE
Read
H6C
to HE1 with the link parameter extended setting = "1", H11 to H23 and H91 to HA3
with the link parameter extended setting = "9").
*6
H00: Frequency
Write
HEC
H01: Parameter-set analog value
H02: Analog value input from terminal
Speed control / position control
Torque limit
RWw2 disabled
RWw2 disabled
Setting range
*1
-400 to 400%
-327.68 to 327.67%
*1
search engine
Data description
H9696: Communication parameters are cleared.
*5
H5A5A
: Communication parameters are not cleared.
H9966: Communication parameters are cleared.
*5
H55AA
: Communication parameters are not cleared.
*7
page
245, and for setting the torque command parameters, refer to
RWw2 function
Torque control
Torque command
Torque command
RWw2 disabled
Actual torque command
page
864.
Actual torque limit
0 to 400%
0 to 327.67%
page