• When using an external power supply for transistor output
Sink logic
Use terminal PC as a common terminal, and perform wiring as
follows. (Do not connect terminal SD on the inverter with the
terminal of 0 V for the external power supply. When using
terminals PC-SD as a 24 VDC power supply, do not install an
external power supply in parallel with the inverter. Doing so
may cause a malfunction in the inverter due to undesirable
currents.)
QY40P type transistor
output unit
Constant
voltage
circuit
2.6.3

Wiring of control circuit

 Control circuit terminal layout
• Recommended cable gauge: 0.3 to 0.75 mm
*1
This terminal operates as terminal FM for the type FM inverter. For the type CA inverter, the terminal operates as terminal CA.
 Wiring method
 Power supply connection
Use crimp terminals and stripped wire for the control circuit wiring. For single wire, the stripped wire can be used without crimp
terminal.
Connect the end of wires (crimp terminal or stranded wire) to the terminal block.
1.
Strip the signal wires as follows. If too much of the wire is stripped, a short circuit may occur with neighboring wires.
If not enough of the wire is stripped, wires may become loose and fall out.
Twist the stripped end of wires to prevent them from fraying. Do not solder them.
74
2. INSTALLATION AND WIRING
2.6 Control circuit
Downloaded from
ManualsNet.com
Inverter
TB1
STF
TB2
STR
TB17
PC
TB18
24 VDC SD
Current flow
2
∗1
2
5
4
1 F/C +24 SD
AM
5 10E 10 SE SE
RUN
SU
Cable sheath stripping length
search engine
Source logic
Use terminal SD as a common terminal, and perform wiring as
follows. (Do not connect terminal PC on the inverter with the
terminal of +24 V for the external power supply. When using
terminals PC-SD as a 24 VDC power supply, do not install an
external power supply in parallel with the inverter. Doing so
may cause a malfunction in the inverter due to undesirable
currents.)
QY80 type transistor
output unit
24 VDC
(SD)
Constant
voltage
circuit
So SOC
SD
SIC
S1 S2 PC
IPF OL FU
PC RL RM RH RT AU
Inverter
PC
TB1
STF
TB2
STR
TB17
Fuse
TB18
SD
Current flow
A1
B1
C1
A2
B2
C2
STP MRS RES
SD SD
STF STR JOG
24 VDC
(SD)
CS