4.
Set the motor capacity and number of motor poles (Pr.80 and Pr.81). (Refer to
V/F control is performed when the setting is "9999" (initial value).
5.
Set the rated motor voltage and the rated motor frequency (Pr.83 and Pr.84). (Refer to
6.
Select the control method (Pr.800). (Refer to
Select Pr.800 = "10" (speed control) or "12" (speed/torque switchover) to enable speed control.
7.
Set the operation command. (Refer to
Select the start command and speed command.
8.
Set the torque limit (Pr.810). (Refer to
9.
Perform the offline auto tuning (Pr.96) (Refer to
10.
Perform the test operation.
As required
• Select online auto tuning (Pr.95) (Refer to
• Perform easy gain tuning. (Refer to
• Adjust the speed control gain manually. (Refer to
NOTE
• During Real sensorless vector control, offline auto tuning must be performed properly before starting operations.
• The speed command setting range under Real sensorless vector control is 0 to 400 Hz.
• The carrier frequency is limited during Real sensorless vector control. (Refer to
• Torque control is not available in a low-speed (about 10 Hz or lower) regenerative range, or with a low speed and light load
(about 5 Hz or lower and rated torque about 20% or lower). Vector control must be selected.
• Performing pre-excitation (LX signal and X13 signal) under torque control may start the motor running at a low speed even
when the start signal (STF or STR) is not input. The inverter at a start command ON may also rotate the motor at a low speed
even though a speed limit value is set to zero. Therefore, confirm that the motor running does not cause any safety problem
before performing pre-excitation.
• Switching between the forward rotation command (STF) and reverse rotation command (STR) must not be performed during
operations under torque control. An overcurrent trip (E.OC[]) or opposite rotation deceleration fault (E.11) will occur.
• When performing continuous operations under Real sensorless vector control in the FR-A820-00250(3.7K) or lower or FR-
A840-00126(3.7K) or lower, the speed fluctuation increases when the value is 20 Hz or less, and in the low-speed range of
less than 1 Hz, there may be torque shortage. In such case, stop the inverter and restart it to improve the situation.
• In case of starting the motor while the motor is coasting under Real sensorless vector control, the frequency search must be
set for the automatic restart after instantaneous power failure function (Pr.57 ≠ "9999", Pr.162 = "10"). (Refer to
• When Real sensorless vector control is applied, there may not be enough torque provided in the ultra low-speed range of about
2 Hz or lower.
Generally, the speed control range is as follows.
For power driving, 1:200 (2, 4 or 6 poles) (available at 0.3 Hz or higher when the rating is 60 Hz), 1:30 (8 poles or more)
(available at 2 Hz or higher when the rating is 60 Hz).
For regenerative driving, 1:12 (2 to 10 poles) (available at 5 Hz or higher when the rating is 60 Hz).
Downloaded from
ManualsNet.com
page
256.)
5.3 Speed control under Real sensorless vector control, vector control, PM sensorless vector control
search engine
page
221.)
page
389.)
page
245.)
page
532.)
page
558.)
page
257.)
page
221.)
page
532.)
page
356.)
5. PARAMETERS
1
2
3
4
5
6
7
8
9
10
page
628.)
241