Mitsubishi Electric FR-A800 Series Instruction Manual page 768

Hide thumbs Also See for FR-A800 Series:
Table of Contents

Advertisement

Example) The output frequency of 60 Hz is indicated as "H1770 (6000)".
SB49
SW0B0.0
0
M0
X20
3
11
 Programming example for the parameter reading
The following program reads Pr.7 Acceleration time of the station 1 inverter to output to D1.
• Pr.7 Acceleration time reading instruction code: H07 (hexadecimal)
• Refer to
page 864
• The reply code (RWr10) to the instruction code execution is set in D2. (Refer to
SW0B0.0
SB49
0
M0
X20
3
M300
7
M301
X1025
9
M302
X1025
16
24
NOTE
• For the parameter assigned the number of 100 or higher, change the link parameter extended setting (set it to the one other
than H00). Refer to
 Programming example for the parameter writing
The following program changes the setting value in Pr.7 Acceleration time of the station 1 inverter to 3.0 seconds.
• Acceleration time writing instruction code: H87 (hexadecimal)
• Acceleration time setting data: K30 (decimal)
For details on instruction codes of each parameter, refer to the list of parameters (function codes) and instruction codes under
different control modes (on
Downloaded from
ManualsNet.com
X1020
for details on the parameter instruction code.
M0
PLS M300
SET M301
MOV H7
W110
SET Y1025
RST M301
SET M302
MOV W11 D1
MOV W10 D2
RST Y1025
RST M302
END
page 864
for the settings.
page
864).
search engine
M0
Check the data link status of the station 1.
Set the monitor code (H01) of output frequency
MOV H1
W126
in RWw26.
Turn ON the monitor command (RY20).
Y1020
Read the output frequency (RWr26) to output to D1
MOV W26 D1
when the monitoring (RX20) turns ON.
END
Check the data link status of the station 1.
Write the Pr. 7 read code (H07) to RWw10.
Turn ON the instruction code execution request (RY25).
Read the acceleration time (RWr11) and the reply code
(RWr10) to output to D1 and D2 when the instruction code
execution completion (RX25) turns ON.
Turn OFF the instruction code execution request (RY25).
page 760
for the reply code (RWr10).)
5. PARAMETERS
5.21 CC-Link IE Field Network (FR-A800-GF)
1
2
3
4
5
6
7
8
9
10
767

Hide quick links: