Response Level Of Analog Input And Noise Elimination - Mitsubishi Electric FR-A800 Series Instruction Manual

Hide thumbs Also See for FR-A800 Series:
Table of Contents

Advertisement

200
150
Pr.252
100
Pr.253
50
0
0V
NOTE
• To use terminal 4, the AU signal needs to be turned ON.
• To make compensation input for multi-speed operation or remote setting, set Pr.28 Multi-speed input compensation
selection = "1" (with compensation) (initial value "0").
• After changing the Pr.73 setting, check the setting of the voltage/current input selection switch. Incorrect setting may cause a
fault, failure, or malfunction. (Refer to
Parameters referred to
Pr.28 Multi-speed input compensation
Pr.73 Analog input
5.12.4 Response level of analog input and noise
The response level and stability of frequency command/torque command using the analog input signal (terminal 1, 2, or 4) can
be adjusted.
Pr.
74
Input filter time constant
T002
822
Speed setting filter 1
T003
826
Torque setting filter 1
T004
832
Speed setting filter 2
T005
836
Torque setting filter 2
T006
849
Analog input offset
T007
adjustment
Downloaded from
ManualsNet.com
Initial value
(50% to 150%)
2.5V
5V
(5V)
(10V)
Voltage across terminals 2 and 5
selectionpage 411
selectionpage 496
elimination
Name
Initial value
1
9999
9999
9999
9999
100%
search engine
• Example) When Pr.73 = "5"
By the terminal 1 (main speed) and terminal 2 (auxiliary) input, the setting
frequency is set as shown in the figure below.
90
60
45
30
15
0
0
Terminal 1 input voltage (V)
page 496
for the setting.)
Setting range
Set the primary delay filter time constant to the analog input
0 to 8
command. If the setting is too large, response becomes
slow.
Set the primary delay filter time constant to the external
0 to 5 s
speed command (analog input command).
9999
As set in Pr.74.
Set the primary delay filter time constant to the external
0 to 5 s
torque command (analog input command).
9999
As set in Pr.74.
Second function of Pr.822 (enabled when the RT signal is
0 to 5 s, 9999
ON)
Second function of Pr.826 (enabled when the RT signal is
0 to 5 s, 9999
ON)
Set offset for the analog speed input (terminal 2). The motor
0 to 200%
is prevented from rotating due to noise in the analog input
or other factors when a zero speed command is given.
Terminal 2 5VDC
input(150%)
Terminal 2 2.5VDC
input(100%)
Terminal 2 0V
input(50%)
2.5
5
Description
5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
1
2
3
4
5
6
7
8
9
10
503

Hide quick links: