Mitsubishi Electric FR-A800 Series Instruction Manual page 512

Hide thumbs Also See for FR-A800 Series:
Table of Contents

Advertisement

Use Pr.73 Analog input selection or Pr.267 Terminal 4 input selection to switch among input 0 to 5 VDC, 0 to 10 V, and 4 to
20 mA. (Refer to
Pr.
C16 (919)
Terminal 1 bias command (torque/
*1
magnetic flux)
T110
C17
Terminal 1 bias (torque/magnetic
(919)
flux)
*1
T111
C18
Terminal 1 gain command (torque/
(920)
magnetic flux)
*1
T112
C19
Terminal 1 gain (torque/magnetic
(920)
flux)
*1
T113
C38
Terminal 4 bias command (torque/
(932)
magnetic flux)
*1
T410
C39
Terminal 4 bias (torque/magnetic
(932)
flux)
*1
T411
C40
Terminal 4 gain command (torque/
(933)
magnetic flux)
*1
T412
C41
Terminal 4 gain (torque/magnetic
(933)
flux)
*1
T413
241
Analog input display unit
M043
switchover
*1
The parameter number in parentheses is the one for use with the LCD operation panel and the parameter unit.
 Changing the function of analog input terminal
• In the initial setting, terminal 1 is used for analog input of the auxiliary speed setting (auxiliary speed limit), and terminal 4
is used for the speed command (speed limit). To use the analog input terminal to input the torque command, torque limit,
or magnetic flux command, set Pr.868 Terminal 1 function assignment or Pr.858 Terminal 4 function assignment to
change the function. (Refer to
Downloaded from
ManualsNet.com
page
496.)
Name
page
500.) The magnetic flux command is valid under Vector control only.
search engine
Initial
Setting range
value
Set the bias torque (magnetic flux) for the terminal 1
0%
0 to 400%
input.
Set the converted % of the bias voltage for the terminal
0%
0 to 300%
1 input.
Set the gain (maximum) torque (magnetic flux) for the
150%
0 to 400%
terminal 1 input.
Set the converted % of the gain voltage for the terminal
100%
0 to 300%
1 input.
Set the bias torque (magnetic flux) for the terminal 4
0%
0 to 400%
input.
Set the converted % of the bias current (voltage) for the
20%
0 to 300%
terminal 4 input.
Set the gain (maximum) torque (magnetic flux) for the
150%
0 to 400%
terminal 4 input.
Set the converted % of the gain current (voltage) for the
100%
0 to 300%
terminal 4 input.
0
% display
0
1
V/mA display
Description
Select the unit for analog input
display.
5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
1
2
3
4
5
6
7
8
9
10
511