The reply code (RWr10) to the instruction code execution is set in D2. (Refer to
SB49
SW0B0.0
0
M0
X20
3
M300
7
M301
X1025
9
M302
X1025
18
24
NOTE
• For the parameter assigned the number of 100 or higher, change the link parameter extended setting (set it to the one other
than H00). Refer to
• For other functions, refer to the instruction codes (refer to
 Programming example for setting the running frequency
The following program changes the running frequency of the station 1 inverter to 50.00 Hz.
• Set frequency: K5000 (decimal)
• The reply code (RWr10) to the instruction code execution is set in D2. (Refer to
SB49
SW0B0.0
0
M0
X20
3
M300
7
M301
X1021
9
M302 X1021
16
22
NOTE
• To change the set frequency continuously from a programmable controller, check that the frequency setting complete (for
example, X1021) turns ON, and the reply code from the intelligent register is H0000. Then change the setting data (for
example, W100) continuously.
• To write the set frequency to the EEPROM, change the following points in the program shown above.
-
Frequency setting command (from Y1021 to Y1022)
-
Frequency setting completion (from X1021 to X1022)
768
5. PARAMETERS
5.21 CC-Link IE Field Network (FR-A800-GF)
Downloaded from
ManualsNet.com
M0
PLS M300
SET M301
MOV H87 W110
MOV K30 W111
SET Y1025
RST M301
SET M302
MOV W10 D2
RST Y1025
RST M302
END
page 864
for the settings.
MOV K5000 W100
MOV W0
search engine
Check the data link status of the station 1.
Write the Pr. 7 write code (H87) to RWw10 and
the acceleration time setting data (K30) to RWw11.
Turn ON the instruction code execution request (RY25).
Read the reply code (RWr10) to output to D2 when the
instruction code execution completion (RX25) turns ON.
Turn OFF the instruction code execution request (RY25).
page
760).
M0
Check the data link status of the station 1.
PLS M300
SET M301
Write the set frequency to RWw0.
SET Y1021
Turn OFF the frequency setting
command RAM (RY21).
RST M301
SET M302
Read the reply code (RWr0) to output to D2 when the
D2
frequency setting completion (RX21) turns ON.
RST Y1021
Turn OFF the frequency setting command RAM
(RY21).
RST M302
END
page 760
for the reply code (RWr10).)
page 760
for the reply code (RWr0).)