• The multifunction regeneration converter (FR-XC in power regeneration mode 1 or 2), power regeneration common
converter (FR-CV), and power regeneration converter (MT-RC) are used for continuous operation during regenerative
driving. The high power factor converter (FR-HC2) and multifunction regeneration converter (FR-XC in common bus
regeneration mode) can also be used to reduce harmonics, improve power factor, and operate continuously during
regenerative driving.
• It is possible to choose between the DC feeding mode 1, which will operate with DC power supply (terminals P and N), and
DC feeding mode 2, which will normally operate in AC power supply (terminals R, S, and T) and operate in DC power
supply (terminal P and N), such as batteries, at the time of power failure.
• While the power is supplied only to the control circuit, the reset operation when the power is supplied to the main circuit
can be selected.
Pr.
30
Regenerative function
E300
selection
70
Special regenerative
*4
brake duty
G107
599
X10 terminal input
T721
selection
*1
The initial value or setting range for the standard model.
*2
The initial value or setting range for the separated converter type.
*3
The initial value or setting range for the IP55 compatible model.
*4
The setting is available for the standard model.
 Details of the setting value
• FR-A820-03160(55K) or lower, FR-A840-01800(55K) or lower
Regeneration unit
*3
Built-in brake
,
brake unit
(FR-BU2 (GZG/GRZG/FR-
BR), FR-BU, BU)
High-duty brake resistor
(FR-ABR)
Multifunction regeneration
converter (FR-XC) (power
regeneration mode 1 or 2)
High power factor converter
(FR-HC2),
multifunction regeneration
converter (FR-XC) (common
bus regeneration mode),
power regeneration common
converter (FR-CV)
Downloaded from
ManualsNet.com
Initial
Name
Setting range
value
0 to 2, 10, 11,
20, 21, 100 to
102, 110, 111,
120, 121
*1*3
0
,
2, 10, 11, 102,
*2
10
110, 111
0, 2, 10, 20,
100, 102, 110,
*3
120
0%
0 to 100%
0
*1*3
0
,
*2
1
1
Power supply
terminals of
inverter
R, S, T
P, N
R, S, T/P, N
R, S, T
P, N
R, S, T/P, N
R, S, T
P, N
search engine
*1
Set the applied regeneration unit, the terminal used for power supply, and
whether to reset the inverter when the power is supplied to the main circuit.
*2
Set the %ED of the built-in brake transistor operation.
Normally open input
Normally closed input (NC contact input specification)
Pr.30
Pr.70
*4
setting
setting
0 (initial
The regenerative brake duty will be as follows.
value), 100
• FR-A820-00046(0.4K) to 00250(3.7K): 3%
• FR-A820-00340(5.5K), 00490(7.5K): 2%
10, 110
• FR-A840-00023(0.4K) to 00250(7.5K): 2%
• Other than above: 0% (without the built-in brake
20, 120
1, 101
*1
10%
The FR-ABR can be used with FR-A820-01250(22K) or
11, 111
*2
lower and the FR-A840-00620(22K) or lower.
6%
21, 121
0 (initial value) —
0% (initial
2, 102
value)
Description
Remarks
resistor)
5.16 (G) Control parameters
1
2
3
4
5
6
7
8
9
10
725
5. PARAMETERS