NOTE
• Pr.184 AU terminal function selection must be set to "4 (initial value)" (AU signal).
• To change the frequency (60 Hz) at the maximum current input (initial value: 20 mA), adjust Pr.126 Terminal 4 frequency
setting gain frequency.
• To change the frequency (0 Hz) at the minimum current input (initial value: 4 mA), adjust the calibration parameter C5
Terminal 4 frequency setting bias frequency.
Parameters referred to
Pr.7 Acceleration time, Pr.8 Deceleration
Pr.79 Operation mode
Pr.126 Terminal 4 frequency setting gain
Pr.184 AU terminal function
C5(Pr.904) Terminal 4 frequency setting bias
154
4. BASIC OPERATION
4.5 Basic operation procedure (PU operation)