Startup Of The Inverter In Network Operation Mode At Power-On - Mitsubishi Electric FR-A800 Series Instruction Manual

Hide thumbs Also See for FR-A800 Series:
Table of Contents

Advertisement

3.
Set "66" in one of Pr.178 to Pr.189 to assign the NET-External operation switching signal (X66) to a terminal.
4.
When the X66 signal is ON, the NET operation mode is selected. When the X66 signal is OFF, the External
operation mode is selected.
Pr.340
Pr.79 setting
setting
0 (initial value)
1
2
3, 4
0 (initial
value), 1, 2
6
7
*1
When Pr.550 NET mode operation command source selection = "0" (communication option control source) and no communication option is
connected, the External operation mode is selected.
*2
When the X16 signal is OFF, the PU operation mode is selected. Also, when the X65 signal is assigned, the operation mode follows the ON/OFF
state of the X65 signal.
NOTE
• The priority of Pr.79 and Pr.340 and signals is as follows: Pr.79 > X12 > X66 > X65 > X16 > Pr.340.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.15 Jog
frequencypage 410
Pr.4 to Pr.6, Pr.24 to Pr.27, Pr.232 to Pr.239 Multi-speed
Pr.75 Reset selection/disconnected PU detection/PU stop
Pr.161 Frequency setting/key lock operation
Pr.178 to Pr.189 (Input terminal function
Pr.190 to Pr.196 (Output terminal function
Pr.340 Communication startup mode
Pr.550 NET mode operation command source
5.9.2
Startup of the inverter in Network operation mode
at power-ON
When power is switched ON or when power comes back ON after an instantaneous power failure, the inverter can be started
up in the Network operation mode.
After the inverter starts up in the Network operation mode, parameter writing and operation can be commanded from programs.
Set this mode when performing communication operation using the RS-485 terminals or a communication option.
Pr.
79
Operation mode selection
D000
340
Communication startup mode
D001
selection
398
5. PARAMETERS
5.9 (D) Operation command and frequency command
Downloaded from
ManualsNet.com
X66 signal state
ON (NET)
NET operation mode
PU operation mode
NET operation mode
External/PU combined operation mode
NET operation mode
X12 (MRS)
NET operation mode
ON
X12 (MRS)
External operation mode
OFF
operationpage 411
selectionpage 336
selectionpage 341
selection)page 521
selection)page 473
selectionpage 398
selectionpage 400
Name
Initial value
0
0
search engine
OFF (External)
External operation
*1
*2
mode
Fixed at PU operation mode.
External operation
*1
Switching to PU operation mode is disabled.
mode
Fixed at External/PU combined operation mode.
External operation
The operation mode can be changed during
*1
*2
operation.
mode
External operation
The signal is OFF during operation in the External
*1
*2
operation mode.
mode
The operation mode is forcibly switched to the
External operation mode.
Setting range
Selects the operation mode.
0 to 4, 6, 7
(Refer to
The inverter starts up in an operation mode selected in
0
Pr.79.
The inverter starts up in the Network operation mode.
If an instantaneous power failure occurs when "2" is
1, 2
set, the operating status before the instantaneous
power failure is maintained.
The inverter starts up in the Network operation mode.
The operation mode can be changed between the PU
operation mode and Network operation mode from the
10, 12
operation panel. If an instantaneous power failure
occurs when "12" is set, running is continued at the
condition before the instantaneous power failure.
Remarks
Description
page
389.)