Mitsubishi Electric FR-A800 Series Instruction Manual page 148

Hide thumbs Also See for FR-A800 Series:
Table of Contents

Advertisement

 Simple mode parameter
Pr.
Pr.
group
0
G000
1
H400
2
H401
3
G001
4
D301
5
D302
6
D303
7
F010
8
F011
H000
9
C103
79
D000
125
T022
126
T042
160
E440
998
E430
999
E431
*1
The initial value for the FR-A820-00077(0.75K) or lower and FR-A840-00038(0.75K) or lower.
*2
The initial value for the FR-A820-00105(1.5K) to FR-A820-00250(3.7K), FR-A840-00052(1.5K) to FR-A840-00126(3.7K).
*3
The initial values for the FR-A820-00340(5.5K), FR-A820-00490(7.5K), FR-A840-00170(5.5K), FR-A840-00250(7.5K).
*4
The initial value for the FR-A820-00630(11K) to FR-A820-03160(55K), FR-A840-00310(11K) to FR-A840-01800(55K).
*5
The initial value for the FR-A820-03800(75K) or higher and FR-A840-02160(75K) and higher.
*6
For the FR-A820-03160(55K) or lower, and FR-A840-01800(55K) or lower.
*7
For the FR-A820-03800(75K) or higher, and FR-A840-02160(75K) or higher.
*8
The initial value for the FR-A820-00077(0.75K) or lower and FR-A840-00038(0.75K) or lower is set to the 85% of the inverter rated current.
*9
The initial value for the FR-A820-00490(7.5K) or lower and FR-A840-00250(7.5K) or lower.
*10 Initial value for the FR-A820-00630(11K) or higher and FR-A840-00310(11K) and higher.
*11 The initial value in "FM" column is for the FM-type inverter that has terminal FM, and that in "CA" column is for the CA-type inverter that has
terminal CA.
Downloaded from
ManualsNet.com
Name
Increment
Torque boost
0.1%
Maximum
0.01 Hz
frequency
Minimum
0.01 Hz
frequency
Base frequency
0.01 Hz
Multi-speed
setting (high
0.01 Hz
speed)
Multi-speed
setting (middle
0.01 Hz
speed)
Multi-speed
0.01 Hz
setting (low speed)
Acceleration time
0.1 s
Deceleration time
0.1 s
*6
0.01 A
Electronic thermal
O/L relay
*7
0.1 A
Operation mode
1
selection
Terminal 2
frequency setting
0.01 Hz
gain frequency
Terminal 4
frequency setting
0.01 Hz
gain frequency
User group read
1
selection
PM parameter
1
initialization
Automatic
1
parameter setting
search engine
*11
Initial value
Range
FM
CA
*1
6%
*2
4%
*3
0 to 30%
3%
*4
2%
*5
1%
*6
120 Hz
0 to 120 Hz
*7
60 Hz
0 Hz
0 to 120 Hz
60 Hz
50 Hz
0 to 590 Hz
60 Hz
50 Hz
0 to 590 Hz
30 Hz
0 to 590 Hz
10 Hz
0 to 590 Hz
*9
5s
0 to 3600 s
*10
15s
*9
5s
0 to 3600 s
*10
15s
*6
Inverter rated
0 to 500 A
*8
current
*7
0 to 3600 A
0
0 to 4, 6, 7
60 Hz
50 Hz
0 to 590 Hz
60 Hz
50 Hz
0 to 590 Hz
0
0, 1, 9999
0, 3003,
3103, 8009,
0
8109, 9009,
9109
1, 2, 10, 11,
9999
12, 13, 20,
21, 9999
4.4 Frequently-used parameters (simple mode parameters)
Application
Set this parameter to obtain a higher starting
torque under V/F control. Also set this when a
loaded motor cannot be driven, the warning
"OL" occurs, and the inverter output is shut off
with the fault indication "E.OC1".
Set the upper limit for the output frequency.
Set the lower limit for the output frequency.
Set this parameter when the rated motor
frequency is 50 Hz. Check the rating plate of
the motor.
Pre-set the speeds that will be switched
among by terminals.
Sets the acceleration time.
Sets the deceleration time.
Protects the motor from heat. Set the rated
motor current.
Select the start and frequency command
sources.
Allows the frequency at the maximum
potentiometer setting (5 V in the initial setting)
to be changed.
Allows the frequency at the maximum current
input (20 mA in the initial setting) to be
changed.
This function restricts the parameters that are
read by the operation panel and parameter
unit.
Selects the PM sensorless vector control and
set the parameters that are required to drive a
PM motor.
Changes parameter settings as a batch. The
target parameters include communication
parameters for the Mitsubishi Electric human
machine interface (GOT) connection and the
parameters for the rated frequency settings of
50/60 Hz.
4. BASIC OPERATION
1
Refer
to
page
2
706
3
4
428
5
707
6
151,
156,
411
7
8
367
9
415
389
10
159,
505
161,
505
354
230
350
147