• Output signal
Signal
FUP
PID upper limit
FUP2
Second PID upper limit
FDN
PID lower limit
FDN2
Second PID lower limit
PID forward/reverse
RL
rotation output
Second PID forward/
RL2
reverse rotation output
During PID control
PID
activated
During second PID
PID2
control activated
Y48
PID deviation limit
Second PID deviation
Y205
limit
SLEEP
PID output interruption
During second PID
SLEEP2
output shutoff
NOTE
• Changing the terminal functions with Pr.178 to Pr.189 and Pr.190 to Pr.196 may affect other functions. Set parameters after
confirming the function of each terminal.
 PID automatic switchover control (Pr.127)
• The system can be started up more quickly by starting up without PID control activated.
• When Pr.127 PID control automatic switchover frequency is set, the startup is made without PID control until the output
frequency reaches the Pr.127 setting. Once the PID control starts, the PID control is continued even if the output frequency
drops to Pr.127 setting or lower.
 Operation selection and sleep function stop selection when a value error
is detected (FUP signal, FDN signal, Y48 signal, Pr.554)
• Using Pr.554 PID signal operation selection, set the action when the measured value input exceeds the upper limit
(Pr.131 PID upper limit) or lower limit (Pr.132 PID lower limit), or when the deviation input exceeds the permissible value
(Pr.553 PID deviation limit).
• Choose whether to output the signals (FUP, FDN, Y48) only or to activate the protective function to output the inverter
shutoff.
608
5. PARAMETERS
5.14 (A) Application parameters
Downloaded from
ManualsNet.com
Pr.190 to Pr.196
setting
Function
Positive
Negative
logic
15
115
201
301
14
114
200
300
16
116
202
302
47
147
203
303
48
148
205
305
70
170
204
304
Output frequency
Without PID
control
Pr.127
STF
PID
search engine
logic
Output when the measured value signal exceeds Pr.131 PID upper limit
(Pr.1143 Second PID upper limit).
Output when the measured value signal falls below Pr.132 PID lower limit
(Pr.1144 Second PID lower limit).
"Hi" is output when the output display of the parameter unit is forward rotation
(FWD) and "Low" is output when the display is reverse rotation (REV) and
stop (STOP).
Turns ON during PID control.
When the PID calculation result is reflected to the output frequency (Pr.128 <
"2000"), the PID signal turns OFF at turn OFF of the start signal.
When the PID calculation result is not reflected to the output frequency
(Pr.128 ≥ "2000"), the PID signal turns ON during PID calculation regardless
of the start signal status.
Output when the absolute deviation value exceeds the limit value set in
Pr.553 PID deviation limit (Pr.1145 Second PID deviation limit).
Set Pr.575 Output interruption detection time (Pr.1147 Second output
interruption detection time) ≠ "9999". This signal turns ON when the PID
output suspension function is activated.
PID control