NOTE
• "
device and try the operation again.
• "
or lower or FR-A840-01800(55K) or lower inverters and the FR-A820-03800(75K) or higher or FR-A840-02160(75K) or higher
inverters. When CP and 0.00 are displayed alternately, set Pr.989 Parameter copy alarm release as shown below (initial
value).
• After setting Pr.989, perform setting of Pr.9, Pr.30, Pr.51, Pr.56, Pr.57, Pr.61, Pr.70, Pr.72, Pr.80, Pr.82, Pr.90 to Pr.94,
Pr.453, Pr.455, Pr.458 to Pr.462, Pr.557, Pr.859, Pr.860, and Pr.893 again.
• When the destination inverter is other than the FR-A800 series or when Parameter copy is attempted after the parameter copy
reading was stopped, the model error "
• Refer to the parameter list on
• When the power is turned OFF or an operation panel is disconnected, etc. during parameter copy writing, write again or check
the setting values by parameter verification.
• When parameters are copied from a different-capacity inverter, there are parameters with different initial values depending on
the inverter capacity, so the setting values of some parameters will be automatically changed. After performing a parameter
copy from a different-capacity inverter, check all the parameter settings. (Refer to the parameter list
parameters with different initial values depending on individual inverter capacity.)
 Procedure for verifying parameters in the USB memory
Operating procedure
1.
Copy the parameter settings of the verification source inverter to the USB memory according to the procedure on
page
2.
Move the USB memory device to the inverter to be verified.
3.
Turning ON the power of the inverter
The operation panel is in the monitor mode.
4.
USB memory mode
Press
5.
Displaying the file selection screen
Press
6.
Selecting the file number
Turn
7.
Parameter verification
Turn
"
Press
the verification destination inverter. (It takes about 15 seconds to verify all the settings. During verification,
"
● If there are different parameters, the different parameter number and "
● To continue verification, press
Downloaded from
ManualsNet.com
" or "
" appears when a USB memory device error occurred. Check the connection of the USB memory
" and "
" are displayed alternately when parameter copy is performed between the FR-A820-03160(55K)
Pr.989 setting
10
Cancels the warning of FR-A820-03160(55K) or lower and FR-A840-01800(55K) or lower.
100
Cancels the warning of FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher.
page 864
748.
to change to the USB memory mode.
three times to display "
to select the file number to be verified, and press
to display the setting "
" appears.
to start verification of the parameter settings copied to the USB memory and the parameter settings of
" blinks.)
search engine
Operation
" appears.
for the availability of parameter copy.
" (file selection screen).
.
" (Parameter copy verification mode), and press
.
5.19 Copying and verifying parameters using a USB memory
(page
166) for details on
" are displayed alternately.
5. PARAMETERS
1
2
3
4
5
6
7
8
9
10
.
749